-- file: ORION-BASE-MIB.mib
-- This MIB file include couple special unicode(UTF-8) characters: ACUTE ACCENT and DEGREE SIGN

ORION-BASE-MIB DEFINITIONS ::= BEGIN

IMPORTS
        DisplayString,
		TEXTUAL-CONVENTION
                FROM SNMPv2-TC
        OBJECT-GROUP,
        NOTIFICATION-GROUP,
        MODULE-COMPLIANCE
                FROM SNMPv2-CONF
        modules,
        orion
                FROM GLOBAL-REG
		InetAddress
				FROM INET-ADDRESS-MIB
        enterprises,
        MODULE-IDENTITY,
        OBJECT-TYPE,
        NOTIFICATION-TYPE,
        Gauge32,
        Integer32,
        IpAddress,
        Unsigned32
                FROM SNMPv2-SMI;

orionBaseMibModule MODULE-IDENTITY
        LAST-UPDATED "201604291257Z"
        ORGANIZATION "Delta Energy Systems (Switzerland) AG"
        CONTACT-INFO
                "postal: Delta Energy Systems (Switzerland) AG
                         Freiburgstrasse 251,
                         CH-3018 Bern-Buempliz
                 web:    www.deltapowersolutions.com
                 email:  adrian.pluess@delta-es.com"
        DESCRIPTION
                "MIB for managing a DC power system with ORION. V6.60B22"

 -- 1.3.6.1.4.1.20246.2.1.1.2 --  
 ::= { modules 2 }
	
-- root for items in the controller MIB module

orionBaseMib OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1 --  
 ::= { orion 1 }

-- conformance area, containing groups and compliance specifications

controllerConfs OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1 --  
 ::= { orionBaseMib 1 }

controllerGroups OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1 --  
 ::= { controllerConfs 1 }

controllerCompl OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.2 --  
 ::= { controllerConfs 2 }

-- sub-tree for objects, and for each functional area

controllerObjects OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2 --  
 ::= { orionBaseMib 2 }

dcSystemInfo OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1 --  
 ::= { controllerObjects 1 }

dcSystemAlarms OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2 --  
 ::= { controllerObjects 2 }

dcSystemMonitor OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3 --  
 ::= { controllerObjects 3 }

dcRectifier OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4 --  
 ::= { controllerObjects 4 }

dcRectifierFunctions OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6 --  
 ::= { dcRectifier 6 }  
 
  dcEfficiencyCycling OBJECT IDENTIFIER 
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1 --  
   ::= { dcRectifierFunctions 1 } 

  dcPowerLimitation OBJECT IDENTIFIER 
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2 --  
   ::= { dcRectifierFunctions 2 } 

dcBattery OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5 --  
 ::= { controllerObjects 5 }

  dcFloatCharge OBJECT IDENTIFIER 
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1 --  
   ::= { dcBattery 1 }

  dcBatteryTest OBJECT IDENTIFIER 
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2 --  
   ::= { dcBattery 2 }

    dcBatteryTestParameter OBJECT IDENTIFIER 
     -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1 --  
     ::= { dcBatteryTest 1 }
     
    dcBatteryTestResults OBJECT IDENTIFIER 
     -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2 --  
     ::= { dcBatteryTest 2 }

  dcBatteryParameter OBJECT IDENTIFIER 
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3 --  
   ::= { dcBattery 3 }   
   
     dcLossOfBackupTime OBJECT IDENTIFIER 
     -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3 --  
     ::= { dcBatteryParameter 3 }

  dcEqualize OBJECT IDENTIFIER 
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4 --  
   ::= { dcBattery 4 }

    dcEqualizeParameter OBJECT IDENTIFIER 
     -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4 --  
     ::= { dcEqualize 4 }
                          
  dcBoostCharge OBJECT IDENTIFIER 
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5 --  
   ::= { dcBattery 5 }

    dcBoostChargeParameter OBJECT IDENTIFIER 
     -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.4 --  
     ::= { dcBoostCharge 4 }
 
  dcSystemVoltageSupervision OBJECT IDENTIFIER 
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6 --  
   ::= { dcBattery 6 }  
   
  dcEvtCtrlCharge OBJECT IDENTIFIER 
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7 --  
   ::= { dcBattery 7 }   

    dcEvtCtrlChargeParameter OBJECT IDENTIFIER 
     -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.3 --  
     ::= { dcEvtCtrlCharge 3 }  
     
  dcTempComp OBJECT IDENTIFIER 
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8 --  
   ::= { dcBattery 8 }   
   
  dcTempSupervision OBJECT IDENTIFIER 
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9 --  
   ::= { dcBattery 9 }   
   
  dcBatteryType OBJECT IDENTIFIER 
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.10 --  
   ::= { dcBattery 10 }   
      
dcInputOutput OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6 --  
 ::= { controllerObjects 6 }
                                    
dcMisc OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7 --  
 ::= { controllerObjects 7 }

dcConfig OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8 --  
 ::= { controllerObjects 8 }
                                    
dcMeasurement OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9 --  
 ::= { controllerObjects 9 }

dcMeterPanel OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10 --  
 ::= { controllerObjects 10 }
 
dcPVC OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11 --  
 ::= { controllerObjects 11 }
 
dcInventory OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.12 --  
 ::= { controllerObjects 12 } 

dcIP OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.13 --  
 ::= { controllerObjects 13 }  
 
  dcIPv4 OBJECT IDENTIFIER 
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.13.1 --  
   ::= { dcIP 1 } 

  dcIPv6 OBJECT IDENTIFIER 
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.13.2 --  
   ::= { dcIP 2 } 

dcAircon OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14 --  
 ::= { controllerObjects 14 }  

dcInverter OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15 --  
 ::= { controllerObjects 15 }
 
-- sub-tree for notifications
controllerEvents OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.3 --  
 ::= { orionBaseMib 3 }

controllerEventObjects OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1 --  
 ::= { controllerEvents 1 }

-- The following OBJECT IDENTIFIER is used to define SNMPv2 notifications
-- that are backward compatible with SNMPv1 traps
controllerEventsV2 OBJECT IDENTIFIER 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0 --  
 ::= { controllerEventObjects 0 }

-- ================================
-- Scalar objects
-- ================================
dcSiteName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (0..128))
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "An administratively-assigned site name for this
                DC-power system."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.1 --  
 ::= { dcSystemInfo 1 }

dcSystemName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (0..128))
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "An administratively-assigned system name for this
                DC-power system."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.2 --  
 ::= { dcSystemInfo 2 }

dcSystemDateTime OBJECT-TYPE
        SYNTAX DisplayString (SIZE (19))
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "ISO 8601 representation of controller's local date/time. 
                The value is in the format YYYY-MM-DDThh:mm:ss. 
                An example of a valid string is: '2004-10-04T13:45:00'."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.3 --  
 ::= { dcSystemInfo 3 }

dcSoftwareVersion OBJECT-TYPE
        SYNTAX DisplayString (SIZE (10..12))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The controller's software version e.g V2.50Build1."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.4 --  
 ::= { dcSystemInfo 4 }

dcCreateInventoryReport OBJECT-TYPE
        SYNTAX INTEGER {
                create(1)
                }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Create the Inventory Report"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.1.5 --  
 ::= { dcSystemInfo 5 }

dcNumberUrgentAlarms OBJECT-TYPE
        SYNTAX Gauge32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Number of currently active urgent alarm sources. A zero 
                value indicates that urgent alarm is not active."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.3 --  
 ::= { dcSystemAlarms 3 }

dcNumberNonUrgentAlarms OBJECT-TYPE
        SYNTAX Gauge32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Number of currently active non urgent alarm sources. A zero 
                value indicates that non urgent alarm is not active."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.4 --  
 ::= { dcSystemAlarms 4 }

dcMainsFailureAlarm OBJECT-TYPE
        SYNTAX INTEGER {
                inactive(1),
                active(2) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Mains failure alarm."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.5 --  
 ::= { dcSystemAlarms 5 }

dcUrgentAlarmIdentifier OBJECT-TYPE
        SYNTAX Gauge32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current unique urgent alarm event identifier. A zero value 
                indicates that urgent alarm is not active."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.6 --  
 ::= { dcSystemAlarms 6 }

dcUrgentAlarmValue OBJECT-TYPE
        SYNTAX INTEGER {
                false(1),
                indeterminate(2),  -- deprecated, not used anymore
                true(3) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current urgent alarm event status that corresponds to the 
                urgent alarm identifier. If the urgent alarm identifier is zero 
                then the alarm value is false."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.7 --  
 ::= { dcSystemAlarms 7 }

dcNonUrgentAlarmIdentifier OBJECT-TYPE
        SYNTAX Gauge32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current unique non urgent alarm event identifier. A zero value 
                indicates that non urgent alarm is not active."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.8 --  
 ::= { dcSystemAlarms 8 }

dcNonUrgentAlarmValue OBJECT-TYPE
        SYNTAX INTEGER {
                false(1),
                indeterminate(2),  -- deprecated, not used anymore
                true(3) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current non urgent alarm event status that corresponds to non urgent 
                alarm identifier. If the non urgent alarm identifier is zero then 
                the alarm value is false."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.9 --  
 ::= { dcSystemAlarms 9 }

dcUrgentAlarmName OBJECT-TYPE
    SYNTAX DisplayString (SIZE (0..35))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current alarm name for urgent alarm that corresponds to urgent 
                alarm identifier."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.10 --  
 ::= { dcSystemAlarms 10 }

dcNonUrgentAlarmName OBJECT-TYPE
    SYNTAX DisplayString (SIZE (0..35))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current alarm name for active non urgent alarm that corresponds 
                to non urgent alarm identifier."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.11 --  
 ::= { dcSystemAlarms 11 }

dcNumberCriticalAlarms OBJECT-TYPE
        SYNTAX Gauge32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Number of currently active critical alarm sources. A zero 
                value indicates that critical alarm is not active."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.13 --  
 ::= { dcSystemAlarms 13 }
 
dcCriticalAlarmIdentifier OBJECT-TYPE
        SYNTAX Gauge32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current unique critical alarm event identifier. A zero value 
                indicates that critical alarm is not active."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.14 --  
 ::= { dcSystemAlarms 14 }

dcCriticalAlarmValue OBJECT-TYPE
        SYNTAX INTEGER {
                false(1),
                indeterminate(2),  -- deprecated, not used anymore
                true(3) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current critical alarm event status that corresponds to the 
                critical alarm identifier. If the critical alarm identifier is zero 
                then the alarm value is false."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.15 --  
 ::= { dcSystemAlarms 15 }

dcCriticalAlarmName OBJECT-TYPE
    SYNTAX DisplayString (SIZE (0..35))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current alarm name for active critical alarm that corresponds 
        to critical alarm identifier."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.16 --  
 ::= { dcSystemAlarms 16 }
 
dcNumberAllAlarms OBJECT-TYPE
        SYNTAX Gauge32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Number of currently active all alarm sources. A zero 
                value indicates that all alarm is not active."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.17 --  
 ::= { dcSystemAlarms 17 }
 
dcAllAlarmIdentifier OBJECT-TYPE
        SYNTAX Gauge32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current unique all alarm event identifier. A zero value 
                indicates that all alarm is not active."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.18 --  
 ::= { dcSystemAlarms 18 }

dcAllAlarmValue OBJECT-TYPE
        SYNTAX INTEGER {
                false(1),
                indeterminate(2),  -- deprecated, not used anymore
                true(3) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current all alarm event status that corresponds to the 
                all alarm identifier. If the all alarm identifier is zero 
                then the alarm value is false."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.19 --  
 ::= { dcSystemAlarms 19 }

dcAllAlarmName OBJECT-TYPE
    SYNTAX DisplayString (SIZE (0..35))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current alarm name for active all alarm that corresponds 
        to all alarm identifier."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.20 --  
 ::= { dcSystemAlarms 20 } 


dcSystemVoltage OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The measured system voltage. The max. value 2147483647 
                is used to indicate an invalid value."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.1 --  
 ::= { dcSystemMonitor 1 }

dcLoadCurrent OBJECT-TYPE
        SYNTAX Integer32
        UNITS "100 mA"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The measured load current. The max. value 2147483647 
                is used to indicate an invalid value."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.2 --  
 ::= { dcSystemMonitor 2 }

dcBatteryCurrent OBJECT-TYPE
        SYNTAX Integer32
        UNITS "100 mA"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION           
                "The measured battery current. The max. value 2147483647 
                is used to indicate an invalid value."  
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.3 --  
 ::= { dcSystemMonitor 3 }

dcBatteryTemperature OBJECT-TYPE
        SYNTAX Integer32
        UNITS "0.1 degree"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The measured battery temperature. The max. value 2147483647 
                is used to indicate an invalid value."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.4 --  
 ::= { dcSystemMonitor 4 }

dcChargeState OBJECT-TYPE
        SYNTAX INTEGER {
                float(1),
                discharge(2),
                equalize(3),
                boost(4),
                battTest(5), 
                recharge(6),
                sepCharge(7),
                evCtrlCharge(8) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Battery charge state."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.5 --  
 ::= { dcSystemMonitor 5 }

dcCurrentLimit OBJECT-TYPE
        SYNTAX INTEGER {
                inactive(1),
                active(2) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Battery current limit."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.6 --  
 ::= { dcSystemMonitor 6 }

dcRectifierCurrent OBJECT-TYPE
        SYNTAX Integer32
        UNITS "100 mA"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION           
                "Total current of all working rectifier modules.
                The maximum value 2147483647 is used to indicate
                an invalid value."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.7 --  
 ::= { dcSystemMonitor 7 }

dcSystemPower OBJECT-TYPE
        SYNTAX Integer32
        UNITS "1 W"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION           
                "Calculated system power. The maximum value 
                2147483647 is used to indicate an invalid value."       
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.3.8 --  
 ::= { dcSystemMonitor 8 }

-- Rectifier
dcNumberRectifiers OBJECT-TYPE
        SYNTAX Gauge32 (0..128)
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The configured number of rectifiers plugged into
                the system. The maximum number of rectifiersi is 128."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.1 --  
 ::= { dcRectifier 1 }

dcNumberRectifiersFailure OBJECT-TYPE
        SYNTAX Gauge32 (0..128)
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Number of rectifiers that are not properly working."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.2 --  
 ::= { dcRectifier 2 }

dcNumberRectifiersOkay OBJECT-TYPE
        SYNTAX Gauge32 (0..128)
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Number of rectifiers that are properly working."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.3 --  
 ::= { dcRectifier 3 }
                      
-- Rectifier - RectifierFunctions - EfficiencyCycling
dcEfficiencyCyclingEnabled OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Enable/disable efficiency cycling."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.1 --  
 ::= { dcEfficiencyCycling 1 } 

dcLimitSwitchingTimes OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Enable/disable limit switching times."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.2 --  
 ::= { dcEfficiencyCycling 2 }
 
dcForceCyclingType OBJECT-TYPE
        SYNTAX INTEGER {
                never(1),
                day(2),
                thirtydays(3) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "If a period is set, then the Force Rectifier Cycling will occur once every period."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.3 --  
 ::= { dcEfficiencyCycling 3 } 
 
dcMinimumPowerReserve OBJECT-TYPE
        SYNTAX Integer32
        UNITS "1 W"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Maximum load setup."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.4 --  
 ::= { dcEfficiencyCycling 4 }
 
dcMinimumRectifierPower OBJECT-TYPE
        SYNTAX Integer32
        UNITS "1 W"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Minimum load setup."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.1.5 --  
 ::= { dcEfficiencyCycling 5 } 

-- Battery - FloatCharge                      
dcUsys20 OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Voltage to regulate to at 20°C(68°F). If temperature compensation
                is used, this voltage will vary."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.1 --  
 ::= { dcFloatCharge 1 }      
 
                                      
-- Battery - BatteryTest - BatteryTestParameter
dcBatteryTestUsupport OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Support charge voltage for the battery."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.1 --  
 ::= { dcBatteryTestParameter 1 }      

dcBatteryTestDuration OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "minute"
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Battery test duration."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.2 --  
 ::= { dcBatteryTestParameter 2 }      
               
dcBatteryTestInterval OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "days"
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Minimal time between programmed battery tests as start 
                condition."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.3 --  
 ::= { dcBatteryTestParameter 3 }      
               
dcBatteryTestDischargeCurrent OBJECT-TYPE
        SYNTAX Integer32
        UNITS "100 mA"
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Battery discharge current. The maximum value 2147483647 
                is used to indicate an invalid value."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.4 --  
 ::= { dcBatteryTestParameter 4 }      
                               
dcBatteryTestMinDuration OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "minutes"
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Minimum battery test duration during which time a battery test 
                is not stopped in case of a voltage below the support voltage or 
                a current difference higher than the specified value defined in 
                Idiff measurement is detected."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.5 --  
 ::= { dcBatteryTestParameter 5 }                              

dcBatteryTestVoltageWithinUfloat OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Battery voltage must be within Ufloat +/- set voltage for a 
                given time (see also dcBatteryTestVoltageWithinUfloatPeriod)
                in order to start a battery test."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.6 --  
 ::= { dcBatteryTestParameter 6 }
 
dcBatteryTestVoltageWithinUfloatPeriod OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "days"
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "For details see dcBatteryTestVoltageWithinUfloat parameter."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.7 --  
 ::= { dcBatteryTestParameter 7 }

dcBatteryTestTempFrom OBJECT-TYPE
        SYNTAX Integer32
        UNITS "0.1 degree"
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Battery temperature must be within temperature range given by
                dcBatteryTestTempFrom and dcBatteryTestTempTo, so that a battery
                test can be started."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.8 --  
 ::= { dcBatteryTestParameter 8 }

dcBatteryTestTempTo OBJECT-TYPE
        SYNTAX Integer32
        UNITS "0.1 degree"
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "For details see dcBatteryTestTempFrom parameter."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.9 --  
 ::= { dcBatteryTestParameter 9 }

dcBatteryTestIntervalEnabled OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Enable/disable interval. For more details see dcBatteryTestInterval."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.1.10 --  
 ::= { dcBatteryTestParameter 10 } 

dcBatteryTestStartTimeFrom OBJECT-TYPE
        SYNTAX DisplayString (SIZE (8))
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Defines start time window for battery test. The possible time window 
                is defined as the range between dcBatteryTestStartTimeFrom and 
                dcBatteryTestStartTimeTo. The value is in the format 'hh:mm:ss'."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.11 --  
 ::= { dcBatteryTestParameter 11 }  
  
dcBatteryTestStartTimeTo OBJECT-TYPE
        SYNTAX DisplayString (SIZE (8))
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "For details see dcBatteryTestStartTimeFrom."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.1.12 --  
 ::= { dcBatteryTestParameter 12 }   
       
-- Battery - BatteryTest - BatteryTestResults
dcBatteryTestDateTime OBJECT-TYPE
        SYNTAX DisplayString (SIZE (19))
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "ISO 8601 representation of the last performed battery test. 
                The value is in the format YYYY-MM-DDThh:mm:ss. This parameter 
                is valid only if there is a test result available."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.1 --  
 ::= { dcBatteryTestResults 1 }      

dcBatteryTestResult OBJECT-TYPE
        SYNTAX INTEGER {
                none(1),
                failed(2),
                aborted(3),
                loadFailure(4),
                okay(5),
                abortedManual(6),
                abortedEvCtrlCharge(7),
                abortedInhibitEv(8) }
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Result of last performed battery test."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.2 --  
 ::= { dcBatteryTestResults 2 }      

dcBatteryTestEndVoltage OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "System voltage at the end of the last performed battery test. 
                The maximum value 2147483647 is used to indicate an invalid 
                value."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.2.3 --  
 ::= { dcBatteryTestResults 3 } 

dcBatteryTestControl OBJECT-TYPE
        SYNTAX INTEGER {
                start(1),
                stop(2) }
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Start/stop of battery test. This special charge mode is used 
                to check the capacity of a battery. Please note that a battery 
                test can be started even if the battery is not fully charged. 
                In this case the test result is ambiguous and the set failure 
                event will become active."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.3 --  
 ::= { dcBatteryTest 3 } 

dcBatteryTestStatus OBJECT-TYPE
        SYNTAX INTEGER {
                inactive(1),
                starting(2),
                stopping(3),
                constantCurrent(4),
                recovery(5),
                realLoad(6)}
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Status of battery test."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.4 --  
 ::= { dcBatteryTest 4 }

dcBatteryTestFailureEvent OBJECT-TYPE
        SYNTAX INTEGER {
                reset(1) }
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Reset battery test failure event."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.5 --  
 ::= { dcBatteryTest 5 }
 
dcBatteryTestType OBJECT-TYPE
        SYNTAX INTEGER {
                none(1),
                constantCurrent(2),
                realLoad(3) }
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Battery test type used."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.6 --  
 ::= { dcBatteryTest 6 } 
 
-- ====================================================================
-- Battery Test table
-- ====================================================================
dcBatteryTestTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcBatteryTestTableEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Lists all the configured Battery Tests elements."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7 --  
 ::= { dcBatteryTest 7 }

dcBatteryTestTableEntry OBJECT-TYPE
        SYNTAX DcBatteryTestTableEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                ""
        INDEX { dcBatteryTestTableIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1 --  
 ::= { dcBatteryTestTable 1 }

DcBatteryTestTableEntry ::= SEQUENCE {		
        dcBatteryTestTableIndex Integer32,
				dcBatteryTestTablePriority Unsigned32,
				dcBatteryTestTableName DisplayString,
				dcBatteryTestTableType INTEGER,
				dcBatteryTestTableStatus INTEGER,
				dcBatteryTestTableUsupport Integer32,
				dcBatteryTestTableDuration Gauge32,           
				dcBatteryTestTableInterval Gauge32,
				dcBatteryTestTableDischargeCurrent Integer32,
				dcBatteryTestTableMinDuration Gauge32,
				dcBatteryTestTableVoltageWithinUfloat Integer32,
				dcBatteryTestTableVoltageWithinUfloatPeriod Gauge32,
				dcBatteryTestTableTempFrom Integer32,
				dcBatteryTestTableTempTo Integer32,
				dcBatteryTestTableIntervalEnabled INTEGER,
				dcBatteryTestTableStartTimeFrom  DisplayString,
				dcBatteryTestTableStartTimeTo DisplayString,
				dcBatteryTestTableControl INTEGER,
				dcBatteryTestTableFailureEvent INTEGER }
 
  dcBatteryTestTableIndex OBJECT-TYPE
        SYNTAX Integer32 (1..10000)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.1 --  
 ::= { dcBatteryTestTableEntry 1 }
 
 dcBatteryTestTablePriority OBJECT-TYPE
        SYNTAX Unsigned32
        MAX-ACCESS read-only   
        STATUS current
        DESCRIPTION
                "Priority of the battery test. Used as index for this table."
  -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.2 --
 ::= { dcBatteryTestTableEntry 2 }

 dcBatteryTestTableName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (32))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Battery test name."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.3 --
 ::= { dcBatteryTestTableEntry 3 }
 
 dcBatteryTestTableType OBJECT-TYPE
        SYNTAX INTEGER {
                none(1),
                constantCurrent(2),
                realLoad(3) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Battery test type used."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.4 -- 
 ::= { dcBatteryTestTableEntry 4 } 
 
 dcBatteryTestTableStatus OBJECT-TYPE
        SYNTAX INTEGER {
                inactive(1),
                starting(2),
                stopping(3),
                constantCurrent(4),
                recovery(5),
                realLoad(6)}
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current status of battery test."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.5 -- 
 ::= { dcBatteryTestTableEntry 5 }
 
dcBatteryTestTableUsupport OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Support charge voltage for the battery."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.6 --  
 ::= { dcBatteryTestTableEntry 6 }      

dcBatteryTestTableDuration OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "minute"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Battery test duration. Zero indicates that this value is not set."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.7 --
 ::= { dcBatteryTestTableEntry 7 }      
               
dcBatteryTestTableInterval OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "days"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Minimal time between programmed battery tests as start 
                condition."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.8 --  
 ::= { dcBatteryTestTableEntry 8 }      
               
dcBatteryTestTableDischargeCurrent OBJECT-TYPE
        SYNTAX Integer32
        UNITS "100 mA"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Battery discharge current. The maximum value 2147483647 
                is used to indicate an invalid value."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.9 --
 ::= { dcBatteryTestTableEntry 9 }      
                               
dcBatteryTestTableMinDuration OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "minutes"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Minimum battery test duration during which time a battery test 
                is not stopped in case of a voltage below the support voltage or 
                a current difference higher than the specified value defined in 
                Idiff measurement is detected."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.10 --
 ::= { dcBatteryTestTableEntry 10 }                              

dcBatteryTestTableVoltageWithinUfloat OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Battery voltage must be within Ufloat +/- set voltage for a given time (see also dcBatteryTestTableVoltageWithinUfloatPeriod) in order to start a battery test."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.11 --
 ::= { dcBatteryTestTableEntry 11 }
 
dcBatteryTestTableVoltageWithinUfloatPeriod OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "days"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "For details see dcBatteryTestTableVoltageWithinUfloat parameter."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.12 --  
 ::= { dcBatteryTestTableEntry 12 }

dcBatteryTestTableTempFrom OBJECT-TYPE
        SYNTAX Integer32
        UNITS "0.1 degree"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Battery temperature must be within temperature range given by dcBatteryTestTableTempFrom and dcBatteryTestTableTempTo, so that a battery test can be started."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.13 --
 ::= { dcBatteryTestTableEntry 13 }

dcBatteryTestTableTempTo OBJECT-TYPE
        SYNTAX Integer32
        UNITS "0.1 degree"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "For details see dcBatteryTestTableTempFrom parameter."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.14 --
 ::= { dcBatteryTestTableEntry 14 }

dcBatteryTestTableIntervalEnabled OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Enable/disable interval. For more details see dcBatteryTestTableInterval."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.15 --  
 ::= { dcBatteryTestTableEntry 15 } 

dcBatteryTestTableStartTimeFrom OBJECT-TYPE
        SYNTAX DisplayString (SIZE (8))
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Defines start time window for battery test. The possible time window is defined as the range between dcBatteryTestTableStartTimeFrom and dcBatteryTestTableStartTimeTo. The value is in the format 'hh:mm:ss'."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.16 --  
 ::= { dcBatteryTestTableEntry 16 }  
  
dcBatteryTestTableStartTimeTo OBJECT-TYPE
        SYNTAX DisplayString (SIZE (8))
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "For details see dcBatteryTestTableStartTimeFrom."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.17 --
 ::= { dcBatteryTestTableEntry 17 }  
 
 dcBatteryTestTableControl OBJECT-TYPE
        SYNTAX INTEGER {
                start(1),
                stop(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Manual Start/stop of battery test."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.18 --
 ::= { dcBatteryTestTableEntry 18 } 
 
 dcBatteryTestTableFailureEvent OBJECT-TYPE
        SYNTAX INTEGER {
                reset(1) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Reset the battery test failure event."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.7.1.19 --
 ::= { dcBatteryTestTableEntry 19 }
 
 
-- ====================================================================
-- Battery Test  Result table
-- ====================================================================
dcBatteryTestResultTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcBatteryTestResultTableEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Lists the results for all configured Battery Test elements."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8 --  
 ::= { dcBatteryTest 8 }
 
dcBatteryTestResultTableEntry OBJECT-TYPE
        SYNTAX DcBatteryTestResultTableEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                ""
        INDEX { dcBatteryTestResultTableIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8.1 --  
 ::= { dcBatteryTestResultTable 1 }

DcBatteryTestResultTableEntry ::= SEQUENCE {		
    dcBatteryTestResultTableIndex Integer32,
		dcBatteryTestResultTablePriority Unsigned32,
		dcBatteryTestResultTableName DisplayString,
		dcBatteryTestResultTableDateTime DisplayString,
		dcBatteryTestResultTableResult INTEGER,
		dcBatteryTestResultTableEndVoltage Integer32	
		}
 
 dcBatteryTestResultTableIndex OBJECT-TYPE
        SYNTAX Integer32 (1..10000)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8.1.1 --  
 ::= { dcBatteryTestResultTableEntry 1 }
 
dcBatteryTestResultTablePriority OBJECT-TYPE
        SYNTAX Unsigned32
        MAX-ACCESS read-only       
        STATUS current
        DESCRIPTION
                "Priority of the battery test. Used as index for this table."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8.1.2 --  
 ::= { dcBatteryTestResultTableEntry 2 }

dcBatteryTestResultTableName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (32))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Battery test name."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8.1.3 --
 ::= { dcBatteryTestResultTableEntry 3 }
 
dcBatteryTestResultTableDateTime OBJECT-TYPE
        SYNTAX DisplayString (SIZE (19))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "ISO 8601 representation of the last performed battery test. The value is in the format YYYY-MM-DDThh:mm:ss. This parameter is valid only if there is a test result available."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8.1.4 --
 ::= { dcBatteryTestResultTableEntry 4 }      

dcBatteryTestResultTableResult OBJECT-TYPE
        SYNTAX INTEGER {
                none(1),
                failed(2),
                aborted(3),
                loadFailure(4),
                okay(5),
                abortedManual(6),
                abortedEvCtrlCharge(7),
                abortedInhibitEv(8) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Result of last performed battery test."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8.1.5 --
 ::= { dcBatteryTestResultTableEntry 5 }      

dcBatteryTestResultTableEndVoltage OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "System voltage at the end of the last performed battery test. 
                The maximum value 2147483647 is used to indicate an invalid 
                value."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.2.8.1.6 --
 ::= { dcBatteryTestResultTableEntry 6 } 
 
-- Battery - BatteryParameter
dcTotalBatteryCapacity OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "100 mAh"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Total battery capacity for all available batteries."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.1 --  
 ::= { dcBatteryParameter 1 }      

-- Battery - BatteryParameter - LossOfBackupTime
dcLossOfBackupTimeEnabled OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Enable/disable loss of backup time functionality."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.1 --
 ::= { dcLossOfBackupTime 1 }

dcLossOfBackupTimeStatus OBJECT-TYPE
        SYNTAX INTEGER {
                inactive(1), 
                ok(2), 
                occured(3), 
                fail(4) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Status of loss of backup time functionality."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.2 --  
 ::= { dcLossOfBackupTime 2 }
 
dcExpectedBackupTime OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "minutes"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Expected backup time value. Based on the given value for 
                the parameter expected backup time, the corresponding 
                maximum discharge current is calculated."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.3.3 --  
 ::= { dcLossOfBackupTime 3 }
 
 -- Battery - BatteryParameter
dcBatteryLifePredictionStatus OBJECT-TYPE
        SYNTAX INTEGER {
            inactive(1), 
            ok(2), 
            warning(3), 
            fail(4) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Battery life prediction status."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.6 --  
 ::= { dcBatteryParameter 6 }  
 
  -- Battery - BatteryParameter
dcBatteryChargingCurrentLimitEnable OBJECT-TYPE
        SYNTAX INTEGER {
            no(1),
            yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Enables the Battery Charging Current limit."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.7 --  
 ::= { dcBatteryParameter 7 }  
 
 -- Battery - BatteryParameter
dcBatteryTotalChargingCurrentLimitEnable OBJECT-TYPE
        SYNTAX INTEGER {
            no(1),
            yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Enables battery charging current limit for total lithium batteries."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.8 --  
 ::= { dcBatteryParameter 8 }  
 
 -- Battery - BatteryParameter
 dcBatteryTotalMaxIBatt OBJECT-TYPE
        SYNTAX Integer32        
        UNITS "100 mA"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Maximum battery charging current for total lithium batteries."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.9 --  
 ::= { dcBatteryParameter 9 }
 
-- Battery - Equalize
dcEqualizeControl OBJECT-TYPE
        SYNTAX INTEGER {
                start(1),
                stop(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Start/stop of battery equalize which is a special charge 
                mode that applies a higher voltage to the batteries than 
                the float charge. This ensures that the cells are all 
                equally charged."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.1 --  
 ::= { dcEqualize 1 } 

dcEqualizeStatus OBJECT-TYPE
        SYNTAX INTEGER {
                inactive(1),
                starting(2),
                stopping(3),
                preparing(4),
                cooking(5),
                recovering(6) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current status of battery equalize."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.2 -- 
 ::= { dcEqualize 2 }
    
dcEqualizeEnabled OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Enable/disable equalize."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.3 --  
 ::= { dcEqualize 3 }

-- Equalize - EqualizeParameter
dcEqualizeVoltage OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Voltage used for equalize."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.1 --  
 ::= { dcEqualizeParameter 1 }
 
dcEqualizeDuration OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "minutes"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Duration of equalize."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.2 --  
 ::= { dcEqualizeParameter 2 }

dcEqualizeUseBattRoomFanEnabled OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Enable/disable battery room fan during equalize."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.3 --  
 ::= { dcEqualizeParameter 3 }

dcEqualizeLeadTime OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "minutes"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Lead time for equalize."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.4 --  
 ::= { dcEqualizeParameter 4 }

dcEqualizeTimeLag OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "minutes"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Time lag for equalize."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.5 --  
 ::= { dcEqualizeParameter 5 }

dcEqualizeInterval OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "days"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Interval for equalize as start condition."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.6 --  
 ::= { dcEqualizeParameter 6 }

dcEqualizeStartTimeIntervalFrom OBJECT-TYPE
        SYNTAX DisplayString (SIZE (8))
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION  
                "Defines start time window for equqlize. The possible time window 
                is defined as the range between dcEqualizeStartTimeIntervalFrom and 
                dcEqualizeStartTimeIntervalTo. The value is in the format 'hh:mm:ss'."               
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.7 --  
 ::= { dcEqualizeParameter 7 }

dcEqualizeStartTimeIntervalTo OBJECT-TYPE
        SYNTAX DisplayString (SIZE (8))
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "For detail see dcEqualizeStartTimeIntervalFrom."               
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.8 --  
 ::= { dcEqualizeParameter 8 }

dcEqualizeInhibitAfterBoost OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "hours"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Inhibit after boost as start condition."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.4.4.9 --   
 ::= { dcEqualizeParameter 9 }

-- Battery - BoostCharge
dcBoostChargeControl OBJECT-TYPE
        SYNTAX INTEGER {
                start(1),
                stop(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Start/stop of boost charge which is a special charge mode 
                that applies a higher voltage to the batteries than the float 
                charge. This mode is started after a discharge phase to 
                recharge the batteries faster."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.1 --  
 ::= { dcBoostCharge 1 } 

dcBoostChargeStatus OBJECT-TYPE
        SYNTAX INTEGER {
                inactive(1),
                starting(2),
                stopping(3),
                cooking(4),
                recovering(5) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current status of boost charge."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2 -- 
 ::= { dcBoostCharge 2 }

dcBoostChargeType OBJECT-TYPE
        SYNTAX INTEGER {
                none(1),
                currentBased(2),
                timeBased(3),
                energyBased(4) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Boost charge type."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.3 -- 
 ::= { dcBoostCharge 3 }

-- Battery - BoostCharge - BoostChargeParameter
dcBoostChargeVoltage OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Voltage used for boost charge."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.1 --  
 ::= { dcBoostChargeParameter 1 }

dcBoostChargeMaxDuration OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "hours"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Defines the maximum allowed time for boost charge to 
                prevent that the battery is charged forever."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.2 --  
 ::= { dcBoostChargeParameter 2 }

dcBoostChargeUseBattRoomFanEnabled OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Enable/disable battery room fan during boost charge."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.3 --  
 ::= { dcBoostChargeParameter 3 }

dcBoostChargeTimeLag OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "minutes"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Time lag used for boost charge."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.4 --  
 ::= { dcBoostChargeParameter 4 }

dcBoostChargeIstart OBJECT-TYPE
        SYNTAX Integer32
        UNITS "100 mA"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "For current based boost charge, the parameters Istart 
                and Istop are the battery current values at which boost charge 
                starts or stops."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.5 --  
 ::= { dcBoostChargeParameter 5 }

dcBoostChargeIstop OBJECT-TYPE
        SYNTAX Integer32
        UNITS "100 mA"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "For details see dcBoostChargeIstart."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.6 --  
 ::= { dcBoostChargeParameter 6 }

dcBoostChargeInhibitTime OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "hours"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "A start condition for all types of boost charge. It defines 
                the time from last boost charge stop to the next acceptable boost 
                charge start."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.7 --  
 ::= { dcBoostChargeParameter 7 }

dcBoostChargeSoCBelow OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "%"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "A start condition for all types of boost charge. It defines 
                the State of Charge (SoC) start condition."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.5.2.8 --  
 ::= { dcBoostChargeParameter 8 }
 
-- Battery - SystemVoltageSupervision
dcUaMax OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "If the system voltage is outside the range specified by the values 
                UaMin (lower alarm voltage)/UaMax (upper alarm voltage), the 
                system event 'S Ua low'/'S Ua high' is activated. The values for the 
                parameters UaMin and UaMax are not temperature compensated."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.1 --  
 ::= { dcSystemVoltageSupervision 1 }     
     
dcUaMin OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "For details see dcUaMax."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.2 --  
 ::= { dcSystemVoltageSupervision 2 }

dcUsMax OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "If the voltage is outside the range defined by the parameters UsMin (lower 
                safety voltage)/UsMax (upper safety voltage), the system event 
                'S Us low'/'S Us high' is activated. If temperature compensation is enabled,
                the levels for Us min and / Us max are automatically temperature compensated 
                to correspond to the required system voltage. The parameters are defined 
                at 20°C(68°F)."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.3 --  
 ::= { dcSystemVoltageSupervision 3 }

dcUsMin OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "For details see dcUsMax."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.4 --  
 ::= { dcSystemVoltageSupervision 4 }
 
dcBoD OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Voltage threshold for Battery on Discharge alarm."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.5 --  
 ::= { dcSystemVoltageSupervision 5 }

dcHysteresis OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Hysteresis used for Ua and Us."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.6 --  
 ::= { dcSystemVoltageSupervision 6 }

dcSuppressUaLowEnabled OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Suppress Ua Low alarm during mains failure."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.7 --  
 ::= { dcSystemVoltageSupervision 7 }

dcSuppressUsLowEnabled OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Suppress Us Low alarm during mains failure."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.8 --  
 ::= { dcSystemVoltageSupervision 8 }
 
dcEnableUsTempComp OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Checkbox to enable the automatic temperature compensation for the Us thresholds (Us min, Us max)."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.6.9 --  
 ::= { dcSystemVoltageSupervision 9 }
       
-- Battery - EvtCtrlCharge
dcEvtCtrlChargeStatus OBJECT-TYPE
        SYNTAX INTEGER {
                inactive(1),
                voltageControlled(2),
                noBatteryCharge(3),
                currentLimitation(4),
                suppressed(5) }
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Event control charge status."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1 --  
 ::= { dcEvtCtrlCharge 1 }

dcEvtCtrlChargeType OBJECT-TYPE
        SYNTAX INTEGER {
                none(1),
                voltageControlled(2),
                noBatteryCharge(3),
                currentLimitation(4) }
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Selected event control charge type."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.2 --  
 ::= { dcEvtCtrlCharge 2 }

dcEvtCtrlChargeVoltage OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Voltage used for event control charge."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1.1 --  
 ::= { dcEvtCtrlChargeParameter 1}

dcEvtCtrlChargeTempCompEnabled OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Enable/disable temperature compensation during event 
                control obsolete."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1.2 --  
 ::= { dcEvtCtrlChargeParameter 2 }

dcEvtCtrlChargeMaxIBatt OBJECT-TYPE
        SYNTAX Integer32
        UNITS "100 mA"
        MAX-ACCESS read-only
        STATUS obsolete
        DESCRIPTION
                "Max. IBatt used for event control charge."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.1.3 --  
 ::= { dcEvtCtrlChargeParameter 3}
 
-- ====================================================================
-- Event controlled charge table
-- ====================================================================
dcEventControlledChargeTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcEventControlledChargeEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Lists all the configured Event Controlled Charges elements."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4 --  
 ::= { dcEvtCtrlCharge 4 }

dcEventControlledChargeTableEntry OBJECT-TYPE
        SYNTAX DcEventControlledChargeEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                ""
        INDEX { dcEventControlledChargeTableIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1 --  
 ::= { dcEventControlledChargeTable 1 }

DcEventControlledChargeEntry ::= SEQUENCE {
				dcEventControlledChargeTableIndex Integer32,
				dcEventControlledChargeTablePriority Unsigned32,
				dcEventControlledChargeTableName DisplayString,
				dcEventControlledChargeTableActivationInput DisplayString,
				dcEventControlledChargeTableStatus INTEGER,
				dcEventControlledChargeTableType INTEGER,
				dcEventControlledChargeTableVoltage Integer32,
				dcEventControlledChargeTableMaxIBatt Integer32,
				dcEventControlledChargeTableTempCompEnabled INTEGER }

dcEventControlledChargeTableIndex OBJECT-TYPE
        SYNTAX Integer32 (1..10000)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.1 --   
 ::= { dcEventControlledChargeTableEntry 1 }

dcEventControlledChargeTablePriority OBJECT-TYPE
        SYNTAX Unsigned32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Priority of the event controlled charge instance. Used as index for this table."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.2 -- 
 ::= { dcEventControlledChargeTableEntry 2 }

dcEventControlledChargeTableName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (32))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Event control charge name."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.3 -- 
 ::= { dcEventControlledChargeTableEntry 3 }
 
 dcEventControlledChargeTableActivationInput OBJECT-TYPE
        SYNTAX DisplayString (SIZE (32))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Event used to activate the controlled charge."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.4 -- 
 ::= { dcEventControlledChargeTableEntry 4 }
 
  dcEventControlledChargeTableStatus OBJECT-TYPE
         SYNTAX INTEGER {
                inactive(1),
                voltageControlled(2),
                noBatteryCharge(3),
                currentLimitation(4),
                suppressed(5) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Event control charge current status."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.5 -- 
 ::= { dcEventControlledChargeTableEntry 5 }
 
 dcEventControlledChargeTableType OBJECT-TYPE
         SYNTAX INTEGER {
                voltageControlled(1),
                noBatteryCharge(2),
                currentLimitation(3) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Selected event control charge type."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.6 -- 
 ::= { dcEventControlledChargeTableEntry 6 }
 
 dcEventControlledChargeTableVoltage OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Voltage used for event control charge."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.7 -- 
 ::= { dcEventControlledChargeTableEntry 7 }
 
  dcEventControlledChargeTableMaxIBatt OBJECT-TYPE
        SYNTAX Integer32
        UNITS "100mA"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Max. IBatt used for event control charge."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.8 -- 
 ::= { dcEventControlledChargeTableEntry 8 }
 
  dcEventControlledChargeTableTempCompEnabled OBJECT-TYPE
         SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Enable/disable temperature compensation during event control charge."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.7.4.1.9 -- 
 ::= { dcEventControlledChargeTableEntry 9 }
 
dcTempCompType OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                linear(2),
                multi-stage(3) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Enable/disable battery temperature compensation."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.1 --  
 ::= { dcTempComp 1 }  
 
dcSlope OBJECT-TYPE
        SYNTAX Integer32
        UNITS "-1 mV/degree"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Temperature compensation coefficient for system voltage."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.2 --  
 ::= { dcTempComp 2 } 
 
dcStartTemp OBJECT-TYPE
        SYNTAX Integer32
        UNITS "0.1 degree"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Lower limit for the area in which the temperature compensation 
                is active."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.3 --  
 ::= { dcTempComp 3 }  

dcStopTemp OBJECT-TYPE
        SYNTAX Integer32
        UNITS "0.1 degree"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Upper limit for the area in which the temperature compensation 
                is active."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.4 --  
 ::= { dcTempComp 4 }  
                    
dcMaxVoltage OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Upper limit for the area in which the temperature compensation 
                is not controlling the system voltage."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.5 --  
 ::= { dcTempComp 5 }
 
dcLowStopVoltage OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "The temperature compensation will not control the charging voltage above this parameter at low temperatures."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.6 --  
 ::= { dcTempComp 6 }
 
dcLowStartTemp OBJECT-TYPE
        SYNTAX Integer32
        UNITS "0.1 degree"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "High temperature limit of the lower range."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.7 --  
 ::= { dcTempComp 7 }  
 
dcLowTempSlope OBJECT-TYPE
        SYNTAX Integer32
        UNITS "-1 mV/degree"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Compensation factor applied inside the low range."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.8 --  
 ::= { dcTempComp 8 } 
 
dcHighStartTemp OBJECT-TYPE
        SYNTAX Integer32
        UNITS "0.1 degree"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "The low temperature limit of the higher range."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.9 --  
 ::= { dcTempComp 9 } 
 
dcHighTempSlope OBJECT-TYPE
        SYNTAX Integer32
        UNITS "-1 mV/degree"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Compensation factor applied inside the high range."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.10 --  
 ::= { dcTempComp 10 } 
 
dcHighStopVoltage OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "The temperature compensation will not control the charging voltage below this parameter at high temperatures."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.11 --  
 ::= { dcTempComp 11 }
 
dcRunawayTemp OBJECT-TYPE
        SYNTAX Integer32
        UNITS "0.1 degree"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "A threshold for detecting thermal runaway of the battery."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.12 --  
 ::= { dcTempComp 12 } 
 
dcRunawayVoltage OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Charging voltage while Runaway Temp has been exceeded."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.8.13 --  
 ::= { dcTempComp 13 } 
 
 dcHighTemp OBJECT-TYPE
        SYNTAX Integer32
        UNITS "0.1 degree"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Temperature threshold for high battery temperature alarm 10°C ... 70°C(50°F ... 158°F)"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9.1 --  
 ::= { dcTempSupervision 1 }  
 
 dcHighTempHyst OBJECT-TYPE
        SYNTAX Integer32
        UNITS "0.1 degree"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Hysteresis for the High Temp 1°C ... 70°C(33.8°F ... 158°F)"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.9.2 --  
 ::= { dcTempSupervision 2 }  
 
  dcBatteryTypeSelect OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                lead-acid(2),
                lithium(3),
                nickel-cadmium(4),
                hybrid-lead-acid(5) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Select Battery Type."      
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.10.1 --  
 ::= { dcBatteryType 1 }  

-- Misc
dcFileProcessingStatus OBJECT-TYPE
        SYNTAX INTEGER {
                idle(1),
                inProgress(2),
                successful(3),
                error(4),
                unknown(5) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "File processing status for software and setup up/downloads."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.2 -- 
 ::= { dcMisc 2 }
 
dcResendActiveAlarmTraps OBJECT-TYPE
        SYNTAX INTEGER {
                resend(1) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Resend all active Urgent, Non Urgent, and Critical Alarm Traps."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.4 --  
 ::= { dcMisc 4 }

dcRebootController OBJECT-TYPE
        SYNTAX INTEGER {
                reboot(1) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Reboot the Controller."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.5 --  
 ::= { dcMisc 5 }
 
-- Event Processing Table 
dcEventProcessingEventSelected OBJECT-TYPE
        SYNTAX Gauge32
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Reference to dcEventProcessingEventIndex in order to select
                a specific event."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.3 --  
 ::= { dcConfig 3 }
                 
-- PVC
dcNumberPVCs OBJECT-TYPE
        SYNTAX Gauge32 (0..32)
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The configured number of PVCs plugged into 
                the system. The maximum number of PVC is 32."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.1 --  
 ::= { dcPVC 1 }

dcNumberPVCsFailure OBJECT-TYPE
        SYNTAX Gauge32 (0..32)
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Number of PVCs that are not properly working."
  -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.2 --
 ::= { dcPVC 2 }

dcNumberPVCsOkay OBJECT-TYPE
        SYNTAX Gauge32 (0..32)
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Number of PVCs that are properly working."
  -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.3 --  
 ::= { dcPVC 3 }
                
-- IPv4
dcIPv4Address OBJECT-TYPE
        SYNTAX InetAddress
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The IP address in IPv4."
  -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.13.1.1 --  
 ::= { dcIPv4 1 }
 
dcIPv4SubnetMask OBJECT-TYPE
        SYNTAX InetAddress
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The subnet mask address in IPv4."
  -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.13.1.2 --  
 ::= { dcIPv4 2 }
 
dcIPv4Gateway OBJECT-TYPE
        SYNTAX InetAddress
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Gateway Address in IPv4."
  -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.13.1.3 --  
 ::= { dcIPv4 3 }
 
dcIPv4DNS OBJECT-TYPE
        SYNTAX InetAddress
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The IP of Domain Name Server in IPv4."
  -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.13.1.4 --  
 ::= { dcIPv4 4 }
 
-- IPv6
dcIPv6LinkLocalAddress OBJECT-TYPE
        SYNTAX InetAddress
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Link Local address."
  -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.13.2.1 --  
 ::= { dcIPv6 1 }
 
dcIPv6Address OBJECT-TYPE
        SYNTAX InetAddress
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The IP address in IPv6."
  -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.13.2.2 --  
 ::= { dcIPv6 2 }
 
dcIPv6Gateway OBJECT-TYPE
        SYNTAX InetAddress
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Gateway address in IPv6."
  -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.13.2.3 --  
 ::= { dcIPv6 3 }
 
dcIPv6DNSAuto OBJECT-TYPE
        SYNTAX InetAddress
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The IP of automatic Domain Name Server in IPv6."
  -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.13.2.4 --  
 ::= { dcIPv6 4 }
 
dcIPv6DNSManual OBJECT-TYPE
        SYNTAX InetAddress
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The IP of manual Domain Name Server in IPv6."
  -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.13.2.5 --  
 ::= { dcIPv6 5 }
				
-- ====================================================================
-- Event History table
-- ====================================================================
dcEventHistoryTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcEventHistoryEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Controller's event history table that shows the content of the
                default log file."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1 --  
 ::= { dcSystemAlarms 1 }

dcEventHistoryEntry OBJECT-TYPE
        SYNTAX DcEventHistoryEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular Event History entry."
        INDEX { dcEventHistoryIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1 --  
 ::= { dcEventHistoryTable 1 }

DcEventHistoryEntry ::= SEQUENCE {

        dcEventHistoryIndex     Integer32,
        dcEventHistoryTimestamp DisplayString,
        dcEventHistoryMessage   DisplayString }

dcEventHistoryIndex OBJECT-TYPE
        SYNTAX Integer32 (1..10000)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.1 --  
 ::= { dcEventHistoryEntry 1 }

dcEventHistoryTimestamp OBJECT-TYPE
        SYNTAX DisplayString (SIZE (19))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "ISO8601 timestamp representation of a particular entry
                in the form YYYY-MM-DDThh:mm:ss."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.2 --  
 ::= { dcEventHistoryEntry 2 }

dcEventHistoryMessage OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..255))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Event message of a particular entry."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.1.1.3 --  
 ::= { dcEventHistoryEntry 3 }


-- ====================================================================
-- Active Alarm table
-- ====================================================================
dcAlarmTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcAlarmEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table that shows all active sent Traps."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2 --  
 ::= { dcSystemAlarms 2 }

dcAlarmEntry OBJECT-TYPE
        SYNTAX DcAlarmEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular active alarm source entry."
        INDEX { dcAlarmIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1 --  
 ::= { dcAlarmTable 1 }

DcAlarmEntry ::= SEQUENCE {
        dcAlarmIndex           Integer32,
        dcAlarmEventCategory   INTEGER,
        dcAlarmEventName       DisplayString,
        dcAlarmEventIdentifier Gauge32, 
        dcAlarmEventValue      INTEGER }

dcAlarmIndex OBJECT-TYPE
        SYNTAX Integer32 (1..16)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.1 --  
 ::= { dcAlarmEntry 1 }

dcAlarmEventCategory OBJECT-TYPE
        SYNTAX INTEGER {
                unknown(1),
                urgent(2),
                nonUrgent(3),
				critical(4),
                allAlarm(5) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Specifies the type of alarm source."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.2 --  
 ::= { dcAlarmEntry 2 }

dcAlarmEventName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..35))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Name of a particular alarm source entry."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.3 --  
 ::= { dcAlarmEntry 3 }

dcAlarmEventIdentifier OBJECT-TYPE
        SYNTAX Gauge32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Unique alarm event identifier."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.4 --  
 ::= {  dcAlarmEntry 4 }

dcAlarmEventValue OBJECT-TYPE
        SYNTAX INTEGER {
                false(1),
                -- indeterminate(2),   deprecated --
                true(3) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Event status that corresponds to alarm event identifier."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.2.1.5 --  
 ::= {  dcAlarmEntry 5 }

-- ====================================================================
-- Generic Alarm table
-- ====================================================================
dcGenericAlarmTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcGenericAlarmEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table that shows ten alarm event assignments that can be 
                 configured via WEB interface."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12 --  
 ::= { dcSystemAlarms 12 }

dcGenericAlarmEntry OBJECT-TYPE
        SYNTAX DcGenericAlarmEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular generic alarm entry."
        INDEX { dcGenericAlarmIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1 --  
 ::= { dcGenericAlarmTable 1 }

DcGenericAlarmEntry ::= SEQUENCE {
        dcGenericAlarmIndex           Integer32,
        dcGenericAlarmEventName       DisplayString,
        dcGenericAlarmEventIdentifier Gauge32, 
        dcGenericAlarmEventValue      INTEGER }

dcGenericAlarmIndex OBJECT-TYPE
        SYNTAX Integer32 (1..16)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.1 --  
 ::= { dcGenericAlarmEntry 1 }
                                                
dcGenericAlarmEventName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (0..35))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Plain text name of the assigned alarm event. Empty if not
                configured."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.2 --  
 ::= { dcGenericAlarmEntry 2 }

dcGenericAlarmEventIdentifier OBJECT-TYPE
        SYNTAX Gauge32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Unique numeric identifier of the assigned alarm event. Zero
                if not configured."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.3 --  
 ::= {  dcGenericAlarmEntry 3 }

dcGenericAlarmEventValue OBJECT-TYPE
        SYNTAX INTEGER {
                false(1),
                true(2) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Current value of the assigned alarm event. Value is false if
                not configured."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.2.12.1.4 --  
 ::= {  dcGenericAlarmEntry 4 }      

-- ====================================================================
-- Rectifier table
-- ====================================================================
dcRectifierTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcRectifierEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table that shows all currently active rectifier modules."
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4 -- 
 ::= { dcRectifier 4 }

dcRectifierEntry OBJECT-TYPE
        SYNTAX DcRectifierEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular rectifier entry."
        INDEX { dcRectifierIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1 --  
 ::= { dcRectifierTable 1 }

DcRectifierEntry ::= SEQUENCE {
        dcRectifierIndex         Integer32, 
        dcRectifierIdentifier    DisplayString, 
        dcRectifierSlotState     INTEGER, 
        dcRectifierMainStatus    INTEGER,
        dcRectifierConfiguration INTEGER,
        dcRectifierIout          Integer32,
        dcRectifierPout          Integer32}

dcRectifierIndex OBJECT-TYPE
        SYNTAX Integer32 (1..128)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.1 --  
 ::= { dcRectifierEntry 1 }
                               
dcRectifierIdentifier OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..16))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Unique rectifier identifier. If positioning active the 
                position number scheme is used otherwise the rectifier 
                instance is used to identify a rectifier."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.2 --  
 ::= { dcRectifierEntry 2 }

dcRectifierSlotState OBJECT-TYPE
        SYNTAX INTEGER {
                noPos(1),
                empty(2),
                lost(3),
                new(4),
                off(5),
                on(6) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Specifies state of slots."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.3 --  
 ::= { dcRectifierEntry 3 }
 
dcRectifierMainStatus OBJECT-TYPE
        SYNTAX INTEGER {
                unknown(1),
                on(2),
                remoteOff(3),
                off(4),
                temporaryInternalOff(5),
                latchedInternalOff(6),
                error(7),
                notAuthenticated(8) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Specifies status of rectifiers."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.4 --  
 ::= { dcRectifierEntry 4 }
 
 dcRectifierConfiguration OBJECT-TYPE
        SYNTAX INTEGER {
                unknown(1),
                ok(2),
                default(3),
                error(4) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Specifies configuration of rectifiers."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.5 --  
 ::= { dcRectifierEntry 5 }
 
 dcRectifierIout OBJECT-TYPE
        SYNTAX Integer32
        UNITS "100 mA"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The measured rectifier output current. The max. value 2147483647 
                is used to indicate an invalid value."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.6 --  
 ::= { dcRectifierEntry 6 }
 
 dcRectifierPout OBJECT-TYPE
        SYNTAX Integer32
        UNITS "W"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The measured rectifier output power. The max. value 2147483647 
                is used to indicate an invalid value."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.4.1.7 --  
 ::= { dcRectifierEntry 7 }
    
-- ====================================================================
-- Rectifier Group table
-- ====================================================================
dcRectifierGroupTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcRectifierGroupEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table that shows all available rectifier groups."
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5 -- 
 ::= { dcRectifier 5 }

dcRectifierGroupEntry OBJECT-TYPE
        SYNTAX DcRectifierGroupEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular rectifier group entry."
        INDEX { dcRectifierGroupIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1 --  
 ::= { dcRectifierGroupTable 1 }

DcRectifierGroupEntry ::= SEQUENCE {
        dcRectifierGroupIndex Integer32, 
        dcRectifierGroupName DisplayString, 
        dcRectifierGroupRectifierType INTEGER,
        dcRectifierGroupDefaultVoltage Integer32,
        dcRectifierGroupDefaultCurrentLimit Integer32,
        dcRectifierGroupDefaultPowerLimit Integer32,
        dcRectifierGroupInputLowOff Integer32,
        dcRectifierGroupInputLowOn Integer32,
        dcRectifierGroupStartupVoltage Integer32,
        dcRectifierGroupStartupCurrentLimit Integer32,
        dcRectifierGroupStartupPowerLimit Integer32,
        dcRectifierGroupStartupLimitTime Gauge32,
        dcRectifierGroupPowerupDelay Gauge32,
        dcRectifierGroupPowerupTime Gauge32,
        dcRectifierGroupUmaxOff Integer32 }

dcRectifierGroupIndex OBJECT-TYPE
        SYNTAX Integer32 (1..1)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.1 --  
 ::= { dcRectifierGroupEntry 1 }
                               
dcRectifierGroupName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..16))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Rectifier group name to identify an individual device 
                parameter set."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.2 --  
 ::= { dcRectifierGroupEntry 2 }

dcRectifierGroupRectifierType OBJECT-TYPE
        SYNTAX INTEGER {
                unknown48V(1), 
                fR48V2000W(2), 
                dPR1200B48(3), 
                dPR1500B48(4), 
                dPR600B48(5),
                dPR7200B48(6),
                fR48to60V2000W(7),
                unknown24V(8),
                unknown60V(9),
                dPR600B60(10),
                dPR3500B48(11),
                dPR3500B24(12),
                dPR300B48(13),
                dPR1600B48(14),
                dPR2700B48(15),
                dPR2400B48(16),
                dPR4000B48(17),
                dPR2900B48(18),
                dPR4000B48to60(19),
                dPR850B48(20),
                dPR2000B48(21),
                dPR6000B48A1(22),
                dPR6000B48B1(23),
                dPR4815B(24),
                dPR24100B(25),
                dPR3000(26),
                eSR4856FF(27),
                dPR2900F48A1(28),
                dPR4000B48A5(29),
                dPR6000B48A1forChineseMarket(30),
                dPR2500F48A1(31),
                dPR3000B48(32),
                dPR1000B48(33),
                dPR12000240(34),
                dPR12000336(35),
                dPR3000B48A4(36),
                dPR1800B48A1(37),
                dPR1800B48A2(38),
                dPR6000B48A2(39)
                 }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Rectifier type defined for this group."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.3 --  
 ::= { dcRectifierGroupEntry 3 }

dcRectifierGroupDefaultVoltage OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "This default voltage is used by rectifiers when there 
                is no connection to ORION."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.4 --  
 ::= { dcRectifierGroupEntry 4 }
 
dcRectifierGroupDefaultCurrentLimit OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "100 mA"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "This default current limit is used by rectifiers when there 
                is no connection to ORION."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.5 --  
 ::= { dcRectifierGroupEntry 5 }

dcRectifierGroupDefaultPowerLimit OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "1 W"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "This default power limit is used by rectifiers when there 
                is no connection to ORION."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.6 --  
 ::= { dcRectifierGroupEntry 6 }
 
dcRectifierGroupInputLowOff OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "100 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Threshold for low AC input voltage. It can is used to 
                adjust the behaviour of the power system to the available 
                AC network limitation."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.7 --  
 ::= { dcRectifierGroupEntry 7 }
    
dcRectifierGroupInputLowOn OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "100 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "For details see dcRectifierGroupInputLowOff."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.8 --  
 ::= { dcRectifierGroupEntry 8 }

dcRectifierGroupStartupVoltage OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Startup parameters are the values that rectifiers use 
                during the start-up phase. These parameters allow starting 
                the system smoothly after a mains failure even on a 
                discharged battery and even without ORION."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.9 --  
 ::= { dcRectifierGroupEntry 9 }

dcRectifierGroupStartupCurrentLimit OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "100 mA"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "For details see dcRectifierGroupStartupVoltage."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.10 --  
 ::= { dcRectifierGroupEntry 10 }

dcRectifierGroupStartupPowerLimit OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "1 W"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "For details see dcRectifierGroupStartupVoltage."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.11 --  
 ::= { dcRectifierGroupEntry 11 }
 
dcRectifierGroupStartupLimitTime OBJECT-TYPE
        SYNTAX Gauge32 
        UNITS "10 ms"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "For details see dcRectifierGroupStartupVoltage."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.12 --  
 ::= { dcRectifierGroupEntry 12 }
 
dcRectifierGroupPowerupDelay OBJECT-TYPE
        SYNTAX Gauge32 
        UNITS "10 ms"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "This parameter is used after a mains failure to 
                delay the start-up of all rectifiers."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.13 --  
 ::= { dcRectifierGroupEntry 13 }

dcRectifierGroupPowerupTime OBJECT-TYPE
        SYNTAX Gauge32 
        UNITS "10 ms"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "This parameter used after a mains failure and allows 
                defining a time within all rectifiers needs to start-up 
                one after another."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.14 -- 
 ::= { dcRectifierGroupEntry 14 }      
 
dcRectifierGroupUmaxOff OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Overvoltage protection value."
                
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.5.1.15 -- 
 ::= { dcRectifierGroupEntry 15 }

-- ====================================================================
-- Rectifier Power Limitation table
-- ====================================================================
dcPowerLimitationTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcPowerLimitationEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table that shows parameters of the available power limitation
                 functions."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2 --   
 ::= { dcPowerLimitation 1 }

dcPowerLimitationEntry OBJECT-TYPE
        SYNTAX DcPowerLimitationEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular power limitation entry."
        INDEX { dcPowerLimitationIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1 --  
 ::= { dcPowerLimitationTable 1 }
 
DcPowerLimitationEntry ::= SEQUENCE {
        dcPowerLimitationIndex     Integer32,
        dcPowerLimitationEventName DisplayString,
        dcPowerLimitationStatus    INTEGER,
        dcPowerLimitationType      INTEGER,
        dcMaxTotalRectifierPower     Integer32,
        dcPowerLimitationNoBatteryDischarge INTEGER }

dcPowerLimitationIndex OBJECT-TYPE
        SYNTAX Integer32 (1..16)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.1 --  
 ::= { dcPowerLimitationEntry 1 }

dcPowerLimitationEventName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..35))        
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Name of the power limitation event."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.2 --
 ::= { dcPowerLimitationEntry 2 }

dcPowerLimitationStatus OBJECT-TYPE
        SYNTAX INTEGER {
                disabled(1), 
                inactive(2), 
                powerLimit(3) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Status of power limitation."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.3 --  
 ::= { dcPowerLimitationEntry 3 } 

dcPowerLimitationType OBJECT-TYPE
        SYNTAX INTEGER {
                dynamic(1), 
                fixedLimit(2) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Power limitation type."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.4 --  
 ::= { dcPowerLimitationEntry 4 } 
 
dcMaxTotalRectifierPower OBJECT-TYPE
        SYNTAX Integer32        
        UNITS "1 W"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Limit used for power limitation."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.5 --  
 ::= { dcPowerLimitationEntry 5 }
 
dcPowerLimitationNoBatteryDischarge OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Enable/disable no battery discharge during power limitation."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.4.6.2.1.6 --  
 ::= { dcPowerLimitationEntry 6 }
 
-- ====================================================================
-- BatteryString table
-- ====================================================================
dcBatteryStringTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcBatteryStringEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table that shows parameters of the available battery strings."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2 --   
 ::= { dcBatteryParameter 2 }

dcBatteryStringEntry OBJECT-TYPE
        SYNTAX DcBatteryStringEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular battery string entry."
        INDEX { dcBatteryStringIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1 --  
 ::= { dcBatteryStringTable 1 }

DcBatteryStringEntry ::= SEQUENCE {
        dcBatteryStringIndex    Integer32,
        dcBatteryStringName     DisplayString,
        dcBatteryStringMaxIBatt Integer32,
        dcBatteryStringCapacity Gauge32 }

dcBatteryStringIndex OBJECT-TYPE
        SYNTAX Integer32 (1..16)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.1 --  
 ::= { dcBatteryStringEntry 1 }
 
dcBatteryStringName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..16))        
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Name of the battery string."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.2 --
 ::= { dcBatteryStringEntry 2 }

dcBatteryStringMaxIBatt OBJECT-TYPE
        SYNTAX Integer32        
        UNITS "100 mA"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Maximum battery charging current for this string. This 
                parameter can be set individually for each battery. 
                ORION then regulates the system voltage such that the maximum 
                battery charging current of each battery is respected."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.3 --  
 ::= { dcBatteryStringEntry 3 }

dcBatteryStringCapacity OBJECT-TYPE
        SYNTAX Gauge32        
        UNITS "100 mAh"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Capacity of battery can be defined individually. It is used 
                to calculate the expected backup time of the system."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.2.1.4 --  
 ::= { dcBatteryStringEntry 4 }

-- ====================================================================
-- BatteryLithium table
-- ====================================================================
dcBatteryLithiumTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcBatteryLithiumEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table that shows parameters of the available Lithium batteries."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4 --   
 ::= { dcBatteryParameter 4 }

dcBatteryLithiumEntry OBJECT-TYPE
        SYNTAX DcBatteryLithiumEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular Lithium battery entry."
        INDEX { dcBatteryLithiumIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1 --  
 ::= { dcBatteryLithiumTable 1 }

DcBatteryLithiumEntry ::= SEQUENCE {
        dcBatteryLithiumIndex            Integer32,
        dcBatteryLithiumName             DisplayString,
        dcBatteryLithiumMainState        INTEGER,
        dcBatteryLithiumSubState         INTEGER,
        dcBatteryLithiumCurrent          Integer32,
        dcBatteryLithiumStateOfCharge    Gauge32,
        dcBatteryLithiumInstallationDate DisplayString,
        dcBatteryLithiumSoH              Gauge32 }

dcBatteryLithiumIndex OBJECT-TYPE
        SYNTAX Integer32 (1..16)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.1 --  
 ::= { dcBatteryLithiumEntry 1 }
 
dcBatteryLithiumName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..16))        
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Name of the Lithium battery."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.2 --
 ::= { dcBatteryLithiumEntry 2 }

dcBatteryLithiumMainState OBJECT-TYPE
        SYNTAX INTEGER {
          invalid(0),     
          unknown(1),
          missing(2),
          ok(3),
          warning(4),
          alarm(5),
          error(6),
          remoteOff(7)}
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Lithium Battery Main State."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.3 -- 
 ::= { dcBatteryLithiumEntry 3 } 
 
dcBatteryLithiumSubState OBJECT-TYPE
        SYNTAX INTEGER {
                invalid(0), 
                na(1),                      
                unknown(2),
                float(3),
                charge(4),
                discharge(5),
                highvoltage(6),
                lowvoltage(7),
                temperature(8),
                highcurrent(9),
                internalfailure(10),
                lowSoC(11)}
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Lithium Battery Sub-State."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.4 -- 
 ::= { dcBatteryLithiumEntry 4 } 
 
dcBatteryLithiumCurrent OBJECT-TYPE
        SYNTAX Integer32        
        UNITS "100 mA"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Lithium battery current"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.5 --  
 ::= { dcBatteryLithiumEntry 5 }
 
dcBatteryLithiumStateOfCharge OBJECT-TYPE
        SYNTAX Gauge32        
        UNITS "%"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Lithium battery state of charge"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.6 --  
 ::= { dcBatteryLithiumEntry 6 }
 
dcBatteryLithiumInstallationDate OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..11))        
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Installation Date of the Lithium battery."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.7 --
 ::= { dcBatteryLithiumEntry 7 }
   
dcBatteryLithiumSoH OBJECT-TYPE
        SYNTAX Gauge32        
        UNITS "%"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Lithium battery state of health."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.8 --  
 ::= { dcBatteryLithiumEntry 8 }
 
 
-- ====================================================================
-- Battery Life Prediction table
-- ====================================================================
dcBatteryLifePredictionTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcBatteryLifePredictionEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table that shows parameters of life prediction."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.5 --   
 ::= { dcBatteryParameter 5 }

dcBatteryLifePredictionEntry OBJECT-TYPE
        SYNTAX DcBatteryLifePredictionEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular life prediction entry."
        INDEX { dcBatteryLifePredictionIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.5.1 --  
 ::= { dcBatteryLifePredictionTable 1 }

DcBatteryLifePredictionEntry ::= SEQUENCE {
        dcBatteryLifePredictionIndex            Integer32,
        dcBatteryLifePredictionName             DisplayString,
        dcBatteryLifePredictionRemainingDays    Gauge32,
        dcBatteryLifePredictionInstallationDate DisplayString,
        dcBatteryLifePredictionSoH              Gauge32 }

dcBatteryLifePredictionIndex OBJECT-TYPE
        SYNTAX Integer32 (1..16)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.1 --  
 ::= { dcBatteryLifePredictionEntry 1 }
 
dcBatteryLifePredictionName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..16))        
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Name of the battery."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.2 --
 ::= { dcBatteryLifePredictionEntry 2 }
 
dcBatteryLifePredictionRemainingDays OBJECT-TYPE
        SYNTAX Gauge32        
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Remaining days of battery."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.3 --  
 ::= { dcBatteryLifePredictionEntry 3 }
 
dcBatteryLifePredictionInstallationDate OBJECT-TYPE
        SYNTAX DisplayString        
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Installation date of battery."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.4 --  
 ::= { dcBatteryLifePredictionEntry 4 }
 
dcBatteryLifePredictionSoH OBJECT-TYPE
        SYNTAX Gauge32        
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Battery state of health."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.5.3.4.1.5 --  
 ::= { dcBatteryLifePredictionEntry 5 }
 
 
-- ====================================================================
-- Control Event table
-- ====================================================================
dcControlEventTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcControlEventEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table that shows ten output event assignments that can be 
                 configured via WEB interface."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1 --   
 ::= { dcInputOutput 1 }

dcControlEventEntry OBJECT-TYPE
        SYNTAX DcControlEventEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular generic output entry."
        INDEX { dcControlEventIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1 --  
 ::= { dcControlEventTable 1 }

DcControlEventEntry ::= SEQUENCE {
        dcControlEventIndex      Integer32,
        dcControlEventName       DisplayString,
        dcControlEventIdentifier Gauge32, 
        dcControlEventValue      INTEGER }

dcControlEventIndex OBJECT-TYPE
        SYNTAX Integer32 (1..16)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.1 --  
 ::= { dcControlEventEntry 1 }

dcControlEventName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (0..35))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Plain text name of the assigned control event. Empty if not 
                configure."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.2 --  
 ::= { dcControlEventEntry 2 }

dcControlEventIdentifier OBJECT-TYPE
        SYNTAX Gauge32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Unique numeric identifier of the assigned control event. Zero
                if not configured."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.3 --  
 ::= {  dcControlEventEntry 3 }

dcControlEventValue OBJECT-TYPE
        SYNTAX INTEGER {
                false(1),
                true(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Current value of the assigned control event. Value is false if
                not configured."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.6.1.1.4 --  
 ::= {  dcControlEventEntry 4 }      
        
-- ====================================================================
-- Trap Destinations table
-- ====================================================================
dcTrapDestinationTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcTrapDestinationEntry
        MAX-ACCESS not-accessible
        STATUS obsolete
        DESCRIPTION
                "Trap table that shows all configured trap destinations."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1 --  
 ::= { dcMisc 1 }

dcTrapDestinationEntry OBJECT-TYPE
        SYNTAX DcTrapDestinationEntry
        MAX-ACCESS not-accessible
        STATUS obsolete
        DESCRIPTION
                "A particular trap destination entry."
        INDEX { dcTrapDestinationIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1 --  
 ::= { dcTrapDestinationTable 1 }

DcTrapDestinationEntry ::= SEQUENCE {
        dcTrapDestinationIndex      Integer32,
        dcTrapDestinationIp         IpAddress,   
        dcTrapDestinationPort       Gauge32,
        dcTrapDestinationUser       DisplayString }

dcTrapDestinationIndex OBJECT-TYPE
        SYNTAX Integer32 (1..10)
        MAX-ACCESS not-accessible
        STATUS obsolete
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.1 --  
 ::= { dcTrapDestinationEntry 1 }

dcTrapDestinationIp OBJECT-TYPE
        SYNTAX IpAddress
        MAX-ACCESS read-write
        STATUS obsolete
        DESCRIPTION
                "IP address of the trap destination. Value is 0.0.0.0 if IP
                address is not configured."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.2 --  
 ::= { dcTrapDestinationEntry 2 }

dcTrapDestinationPort OBJECT-TYPE
        SYNTAX Gauge32
        MAX-ACCESS read-write
        STATUS obsolete
        DESCRIPTION
                "Port number of the trap destination. By default port 162
                is used."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.3 --  
 ::= {  dcTrapDestinationEntry 3 }
 
dcTrapDestinationUser OBJECT-TYPE
        SYNTAX DisplayString (SIZE (0..32))
        MAX-ACCESS read-write
        STATUS obsolete
        DESCRIPTION
                "User of the trap destination."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.1.1.4 --  
 ::= {  dcTrapDestinationEntry 4 }
 
-- ====================================================================
-- Trap Destinations table version 2
-- ====================================================================
dcTrapDestinationv2Table OBJECT-TYPE
        SYNTAX SEQUENCE OF DcTrapDestinationv2Entry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Trap table that shows all configured trap destinations."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.6 --  
 ::= { dcMisc 6 }

dcTrapDestinationv2Entry OBJECT-TYPE
        SYNTAX DcTrapDestinationv2Entry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A specific trap destination entry."
        INDEX { dcTrapDestinationv2Index }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.6.1 --  
 ::= { dcTrapDestinationv2Table 1 }

DcTrapDestinationv2Entry ::= SEQUENCE {
        dcTrapDestinationv2Index      Integer32,
        dcTrapDestinationv2           DisplayString,   
        dcTrapDestinationv2Port       Gauge32,
        dcTrapDestinationv2User       DisplayString }

dcTrapDestinationv2Index OBJECT-TYPE
        SYNTAX Integer32 (1..10)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.6.1.1 --  
 ::= { dcTrapDestinationv2Entry 1 }

dcTrapDestinationv2 OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Address of the trap destination."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.6.1.2 --  
 ::= { dcTrapDestinationv2Entry 2 }

dcTrapDestinationv2Port OBJECT-TYPE
        SYNTAX Gauge32
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Port number of the trap destination."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.6.1.3 --  
 ::= {  dcTrapDestinationv2Entry 3 }
 
dcTrapDestinationv2User OBJECT-TYPE
        SYNTAX DisplayString (SIZE (0..32))
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "User of the trap destination."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.7.6.1.4 --  
 ::= {  dcTrapDestinationv2Entry 4 }
 
-- ====================================================================
-- Default Log Config table
-- ====================================================================
dcDefaultLogEventTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcDefaultLogEventEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Event config table for default log."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1 --  
 ::= { dcConfig 1 }

dcDefaultLogEventEntry OBJECT-TYPE

        SYNTAX DcDefaultLogEventEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular event entry."
        INDEX { dcDefaultLogEventIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1 --  
 ::= { dcDefaultLogEventTable 1 }

DcDefaultLogEventEntry ::= SEQUENCE {
        dcDefaultLogEventIndex  Integer32,
        dcDefaultLogEventName   DisplayString,   
        dcDefaultLogEventLogged INTEGER }

dcDefaultLogEventIndex OBJECT-TYPE
        SYNTAX Integer32 (0..1000)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.1 --  
 ::= { dcDefaultLogEventEntry 1 }

dcDefaultLogEventName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..35))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Plain text name of the event that can be logged."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.2 --  
 ::= { dcDefaultLogEventEntry 2 }

dcDefaultLogEventLogged OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "If yes then this event is logged otherwise not."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.1.1.3 --  
 ::= {  dcDefaultLogEventEntry 3 }

-- ====================================================================
-- Event Processing Config table
-- ====================================================================
dcEventProcessingEventTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcEventProcessingEventEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Event config table for event ORs."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2 --  
 ::= { dcConfig 2 }

dcEventProcessingEventEntry OBJECT-TYPE
        SYNTAX DcEventProcessingEventEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular event entry."
        INDEX { dcEventProcessingEventIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1 --  
 ::= { dcEventProcessingEventTable 1 }

DcEventProcessingEventEntry ::= SEQUENCE {
        dcEventProcessingEventIndex  Integer32,
        dcEventProcessingEventName   DisplayString,   
        dcEventProcessingEventAssigned INTEGER,
        dcEventProcessingEventType INTEGER }

dcEventProcessingEventIndex OBJECT-TYPE
        SYNTAX Integer32 (0..1000)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.1 --  
 ::= { dcEventProcessingEventEntry 1 }

dcEventProcessingEventName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..35))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Plain text name of the input event."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.2 --  
 ::= { dcEventProcessingEventEntry 2 }

dcEventProcessingEventAssigned OBJECT-TYPE
        SYNTAX INTEGER {
                no(1),
                yes(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "If yes then the input event is assigned to the selected 
                event. Please note, that it is only possible to change 
                assignment of event ORs."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.3 --  
 ::= {  dcEventProcessingEventEntry 3 }

dcEventProcessingEventType OBJECT-TYPE
        SYNTAX INTEGER {
                unknown(1),
                eventOR(2) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Type of the input event."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.2.1.4 --  
 ::= {  dcEventProcessingEventEntry 4 }

-- ====================================================================
-- LVD Config table
-- ====================================================================
dcLvdTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcLvdEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table lists all available LVDs."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4 --  
 ::= { dcConfig 4 }

dcLvdEntry OBJECT-TYPE
        SYNTAX DcLvdEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular LVD entry."
        INDEX { dcLvdIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1 --  
 ::= { dcLvdTable 1 }

DcLvdEntry ::= SEQUENCE {
        dcLvdIndex Integer32,
        dcLvdName DisplayString,   
        dcLvdDisconnectDelay DisplayString,
		dcLvdType INTEGER, 
		dcLvdVoltageThreshold Integer32,	
		dcLvdVoltageHysteresis Integer32,
		dcLvdControlEvent DisplayString,	
		dcLvdMonitoringEvent DisplayString}

dcLvdIndex OBJECT-TYPE
        SYNTAX Integer32 (1..96)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.1 --  
 ::= { dcLvdEntry 1 }

dcLvdName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..16))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Name of the LVD."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.2 --  
 ::= { dcLvdEntry 2 }

dcLvdDisconnectDelay OBJECT-TYPE
        SYNTAX DisplayString (SIZE (8))
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Time delay from the activation of the source event, after 
                which the LVD event is switched. The value is in the format 
                'hh:mm:ss'."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.3 -- 
 ::= {  dcLvdEntry 3 }
 
 dcLvdType OBJECT-TYPE
        SYNTAX INTEGER {
                eventControlled(1),
                utControlled(2) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Type of the LVD."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.4 --  
 ::= {  dcLvdEntry 4 }
 
dcLvdVoltageThreshold OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Voltage threshold for U and t controlled type LVD. Only available in U and t Controlled Type LVDs."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.5 -- 
 ::= {  dcLvdEntry 5 }
 
dcLvdVoltageHysteresis OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Voltage Hysteresis for U and t controlled type LVD. Only available in U and t Controlled Type LVDs."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.6 -- 
 ::= {  dcLvdEntry 6 }
 
  dcLvdControlEvent OBJECT-TYPE
        SYNTAX DisplayString (SIZE (0..35))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Control (previously named Source) Event for the LVD action. Only available in Event Controlled Type LVDs."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.7 -- 
 ::= {  dcLvdEntry 7 }
 
 dcLvdMonitoringEvent OBJECT-TYPE
        SYNTAX DisplayString (SIZE (0..35))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Monitoring Event. Only available in Event Controlled Type LVDs."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.4.1.8 -- 
 ::= {  dcLvdEntry 8 }

-- ====================================================================
-- EventDefinition table
-- ====================================================================
dcEventDefinitionTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcEventDefinitionEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table that shows twenty threshold event assignments that can be 
                 configured via WEB interface."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5 --  
 ::= { dcConfig 5 }

dcEventDefinitionEntry OBJECT-TYPE
        SYNTAX DcEventDefinitionEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular generic EventDefinition entry."
        INDEX { dcEventIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5.1 --  
 ::= { dcEventDefinitionTable 1 }

DcEventDefinitionEntry ::= SEQUENCE {
        dcEventIndex             Integer32,
        dcEventName              DisplayString,
        dcThreshold              Integer32, 
		dcThresholdHysteresis    Integer32,
        dcUnit                   INTEGER }

dcEventIndex OBJECT-TYPE
        SYNTAX Integer32 (1..20)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5.1.1 --  
 ::= { dcEventDefinitionEntry 1 }
                                                
dcEventName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (0..35))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Name of the threshold."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5.1.2 --  
 ::= { dcEventDefinitionEntry 2 }

dcThreshold OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Value of the threshold."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5.1.3 --  
 ::= { dcEventDefinitionEntry 3 }

dcThresholdHysteresis OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Hysteresis of the threshold."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5.1.4 --  
 ::= { dcEventDefinitionEntry 4 }    

dcUnit OBJECT-TYPE
                SYNTAX INTEGER {
                unitUnknown(1), 
                unitNone(2),
                unit10mVdc(3),
                unit10mVac(4),
                unit100mA(5),
                unit100mAh(6),
                unit100mDegree(7),
                unit100mDegreeCoefficient(8),
                unitWatt(9),
                unitWattHour(10),
				unitKilowattHour(11),
                unitSeconds(12),
                unitPercent(13),
                unitHertz(14),
                unitVoltAmpere(15),
                unitVoltAmpereReactive(16), 
                unitVoltAmpereReactiveHour(17),
                unitVoltAmpereHour(18) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Unit of the threshold"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5.1.5 --  
 ::= { dcEventDefinitionEntry 5 }  

-- ====================================================================
-- Filter table
-- ====================================================================
dcFilterTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcFilterEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table that shows twenty filter event assignments that can be 
                 configured via WEB interface."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.6 --  
 ::= { dcConfig 6 }

dcFilterEntry OBJECT-TYPE
        SYNTAX DcFilterEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular generic Filter entry."
        INDEX { dcFilterIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.6.1 --  
 ::= { dcFilterTable 1 }

DcFilterEntry ::= SEQUENCE {
        dcFilterIndex            Integer32,
        dcFilterName             DisplayString,
		dcTrueForMin		     DisplayString,
        dcFalseForMin            DisplayString }

dcFilterIndex OBJECT-TYPE
        SYNTAX Integer32 (1..20)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.6.1.1 --  
 ::= { dcFilterEntry 1 }
                                                
dcFilterName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (0..35))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Name of the Filter."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.6.1.2 --  
 ::= { dcFilterEntry 2 }

dcTrueForMin OBJECT-TYPE
        SYNTAX DisplayString (SIZE (0..35))
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "True for Min."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5.1.3 --  
 ::= { dcFilterEntry 3 }

dcFalseForMin OBJECT-TYPE
        SYNTAX DisplayString (SIZE (0..35))
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "False for Min."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.5.1.4 --  
 ::= { dcFilterEntry 4 }    
 
-- ====================================================================
-- Timer table
-- ====================================================================
dcTimerTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcTimerEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table that shows twenty timer event assignments that can be 
                 configured via WEB interface."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7 --  
 ::= { dcConfig 7 }

dcTimerEntry OBJECT-TYPE
        SYNTAX DcTimerEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular generic Timer entry."
        INDEX { dcTimerIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1 --  
 ::= { dcTimerTable 1 }

DcTimerEntry ::= SEQUENCE {
        dcTimerIndex             Integer32,
        dcTimerName              DisplayString,
		dcStartTime              DisplayString,
		dcStartDaySu			 INTEGER,
		dcStartDayMo			 INTEGER,
		dcStartDayTu			 INTEGER,
		dcStartDayWe			 INTEGER,
		dcStartDayTh			 INTEGER,
		dcStartDayFr			 INTEGER,
		dcStartDaySa			 INTEGER,
		dcEndTime                DisplayString,
		dcEndDaySu			 	 INTEGER,
		dcEndDayMo			 	 INTEGER,
		dcEndDayTu			 	 INTEGER,
		dcEndDayWe			 	 INTEGER,
		dcEndDayTh			 	 INTEGER,
		dcEndDayFr			 	 INTEGER,
		dcEndDaySa			 	 INTEGER}

dcTimerIndex OBJECT-TYPE
        SYNTAX Integer32 (1..20)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.1 --  
 ::= { dcTimerEntry 1 }
                                                
dcTimerName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (0..35))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Name of the Timer."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.2 --  
 ::= { dcTimerEntry 2 }

dcStartTime OBJECT-TYPE
        SYNTAX DisplayString (SIZE (0..10))
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Start Time(hh:mm)."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.3 --  
 ::= { dcTimerEntry 3 }

dcStartDaySu OBJECT-TYPE
        SYNTAX INTEGER {no(1), yes(2)}
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Is Sunday Start Day?"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.4 --  
 ::= { dcTimerEntry 4 }

dcStartDayMo OBJECT-TYPE
        SYNTAX INTEGER {no(1), yes(2)}
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Is Monday Start Day?"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.5 -- 
 ::= { dcTimerEntry 5 }

dcStartDayTu OBJECT-TYPE
        SYNTAX INTEGER {no(1), yes(2)}
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Is Tuesday Start Day?"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.6 --  
 ::= { dcTimerEntry 6 } 

dcStartDayWe OBJECT-TYPE
        SYNTAX INTEGER {no(1), yes(2)}
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Is Wednesday Start Day?"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.7 --  
 ::= { dcTimerEntry 7 } 

dcStartDayTh OBJECT-TYPE
        SYNTAX INTEGER {no(1), yes(2)}
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Is Thursday Start Day?"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.8 --
 ::= { dcTimerEntry 8 } 

 dcStartDayFr OBJECT-TYPE
        SYNTAX INTEGER {no(1), yes(2)}
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Is Friday Start Day?"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.9 --   
 ::= { dcTimerEntry 9 }    
 
dcStartDaySa OBJECT-TYPE
        SYNTAX INTEGER {no(1), yes(2)}
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Is Saturday Start Day?"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.10 --   
 ::= { dcTimerEntry 10 }    

dcEndTime OBJECT-TYPE
        SYNTAX DisplayString (SIZE (0..10))
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "End Time(hh:mm)."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.11 --  
 ::= { dcTimerEntry 11 }

dcEndDaySu OBJECT-TYPE
        SYNTAX INTEGER {no(1), yes(2)}
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Is Sunday End Day?"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.12 --  
 ::= { dcTimerEntry 12 }

dcEndDayMo OBJECT-TYPE
        SYNTAX INTEGER {no(1), yes(2)}
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Is Monday End Day?"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.13 -- 
 ::= { dcTimerEntry 13 }

dcEndDayTu OBJECT-TYPE
        SYNTAX INTEGER {no(1), yes(2)}
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Is Tuesday End Day?"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.14 --  
 ::= { dcTimerEntry 14 } 

dcEndDayWe OBJECT-TYPE
        SYNTAX INTEGER {no(1), yes(2)}
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Is Wednesday End Day?"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.15 --  
 ::= { dcTimerEntry 15 } 

dcEndDayTh OBJECT-TYPE
        SYNTAX INTEGER {no(1), yes(2)}
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Is Thursday End Day?"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.16 --
 ::= { dcTimerEntry 16 } 

 dcEndDayFr OBJECT-TYPE
        SYNTAX INTEGER {no(1), yes(2)}
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Is Friday End Day?"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.17 --   
 ::= { dcTimerEntry 17 }    
 
dcEndDaySa OBJECT-TYPE
        SYNTAX INTEGER {no(1), yes(2)}
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Is Saturday End Day?"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.8.7.1.18 --   
 ::= { dcTimerEntry 18 }
 
-- ====================================================================
-- Measurement table
-- ====================================================================
dcMeasurementTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcMeasurementEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table lists all available measurements."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1 --    
 ::= { dcMeasurement 1 }

dcMeasurementEntry OBJECT-TYPE
        SYNTAX DcMeasurementEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular measurement entry."
        INDEX { dcMeasurementIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1 -- 
 ::= { dcMeasurementTable 1 }

DcMeasurementEntry ::= SEQUENCE {
        dcMeasurementIndex Integer32,
        dcMeasurementName DisplayString,
        dcMeasurementValue Integer32, 
        dcMeasurementScaleFactor Integer32,
        dcMeasurementUnit INTEGER }

dcMeasurementIndex OBJECT-TYPE
        SYNTAX Integer32 (1..500)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.1 --  
 ::= { dcMeasurementEntry 1 }

dcMeasurementName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..16))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Name of the measurement."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.2 --  
 ::= { dcMeasurementEntry 2 }

dcMeasurementValue OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Unscaled calibrated value of the measurement."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.3 --  
 ::= { dcMeasurementEntry 3 }     
 
dcMeasurementScaleFactor OBJECT-TYPE
        SYNTAX Integer32
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Scale factor as power of 10 to be multiplied with measurement value."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.4 --  
 ::= { dcMeasurementEntry 4 }
 
dcMeasurementUnit OBJECT-TYPE
        SYNTAX INTEGER {
                unknown(1), 
                none(2),
                voltDC(3),
                voltAC(4),
                ampere(5),
                ampereHour(6),
                temperature(7),
                temperatureCoefficient(8),
                watt(9),
                wattHour(10),
                seconds(11),
                percent(12),
                hertz(13),
                voltAmpere(14),
                voltAmpereReactive(15), 
                voltAmpereReactiveHour(16),
                voltAmpereHour(17) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Unit of the measurement."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.9.1.1.5 --  
 ::= { dcMeasurementEntry 5 }

-- ====================================================================
-- Meter Panel Event table
-- ====================================================================
dcMeterPanelEventTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcMeterPanelEventEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table lists all available meter panel events."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1 --    
 ::= { dcMeterPanel 1 }

dcMeterPanelEventEntry OBJECT-TYPE
        SYNTAX DcMeterPanelEventEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular meter panel event entry."
        INDEX { dcMeterPanelEventIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1 -- 
 ::= { dcMeterPanelEventTable 1 }

DcMeterPanelEventEntry ::= SEQUENCE {
        dcMeterPanelEventIndex Integer32,
        dcMeterPanelEventName DisplayString,
        dcMeterPanelEventValue INTEGER,
        dcMeterPanelEventHourMeterValue Gauge32 }

dcMeterPanelEventIndex OBJECT-TYPE
        SYNTAX Integer32 (1..128)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.1 --  
 ::= { dcMeterPanelEventEntry 1 }

dcMeterPanelEventName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..16))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Name of the event."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.2 --  
 ::= { dcMeterPanelEventEntry 2 }
                                       
dcMeterPanelEventValue OBJECT-TYPE
        SYNTAX INTEGER {
                false(1),
                indeterminate(2),
                true(3) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Value of the event."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.3 --  
 ::= { dcMeterPanelEventEntry 3 }     

dcMeterPanelEventHourMeterValue OBJECT-TYPE
        SYNTAX Gauge32
        UNITS "seconds"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Value of the hour meter event."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.1.1.4 --  
 ::= { dcMeterPanelEventEntry 4 } 

-- ====================================================================
-- Meter Panel Measurement table
-- ====================================================================
dcMeterPanelMeasurementTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcMeterPanelMeasurementEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table lists all available meter panel Measurements."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.2 --    
 ::= { dcMeterPanel 2 }

dcMeterPanelMeasurementEntry OBJECT-TYPE
        SYNTAX DcMeterPanelMeasurementEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular meter panel Measurement entry."
        INDEX { dcMeterPanelMeasurementIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.2.1 -- 
 ::= { dcMeterPanelMeasurementTable 1 }

DcMeterPanelMeasurementEntry ::= SEQUENCE {
        dcMeterPanelMeasurementIndex Integer32,
        dcMeterPanelMeasurementName DisplayString,
        dcMeterPanelMeasurementValue DisplayString,
        dcMeterPanelMeasurementUnit DisplayString }

dcMeterPanelMeasurementIndex OBJECT-TYPE
        SYNTAX Integer32 (1..128)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.2.1.1 --  
 ::= { dcMeterPanelMeasurementEntry 1 }

dcMeterPanelMeasurementName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..16))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Name of the Measurement."

 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.2.1.2 --  
 ::= { dcMeterPanelMeasurementEntry 2 }     

dcMeterPanelMeasurementValue OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Value of the Measurement."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.2.1.3 --  
 ::= { dcMeterPanelMeasurementEntry 3 } 
 
dcMeterPanelMeasurementUnit OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..16))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Unit of the measurement."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.10.2.1.4 --  
 ::= { dcMeterPanelMeasurementEntry 4 } 

-- ====================================================================
-- PVC table
-- ====================================================================
dcPVCTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcPVCEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table that shows all currently active PVC modules."
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4 -- 
 ::= { dcPVC 4 }

dcPVCEntry OBJECT-TYPE
        SYNTAX DcPVCEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular PVC entry."
        INDEX { dcPVCIndex } 
  -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1 -- 
 ::= { dcPVCTable 1 }

DcPVCEntry ::= SEQUENCE {
        dcPVCIndex         Integer32, 
        dcPVCIdentifier    DisplayString, 
        dcPVCSlotState     INTEGER, 
        dcPVCMainStatus    INTEGER,
        dcPVCSubStatus     INTEGER,
        dcPVCConfiguration INTEGER,
        dcPVCIout          Integer32,
        dcPVCUout          Integer32,
        dcPVCIin           Integer32,
        dcPVCUin           Integer32}

dcPVCIndex OBJECT-TYPE
        SYNTAX Integer32 (1..32)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.1 -- 
 ::= { dcPVCEntry 1 }
                               
dcPVCIdentifier OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..16))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Unique PVC identifier. If positioning active the 
                position number scheme is used otherwise the PVC 
                instance is used to identify a PVC."
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.2 --  
 ::= { dcPVCEntry 2 }

dcPVCSlotState OBJECT-TYPE
        SYNTAX INTEGER {
                noPos(1),
                empty(2),
                lost(3),
                new(4),
                off(5),
                on(6) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Specifies state of slots."
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.3 --  
 ::= { dcPVCEntry 3 }
 
dcPVCMainStatus OBJECT-TYPE
        SYNTAX INTEGER {
                unknown(1),
                on(2),
                remoteOff(3),
                off(4),
                temporaryInternalOff(5),
                latchedInternalOff(6),
                error(7) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Specifies status of PVCs."
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.4 -- 
 ::= { dcPVCEntry 4 }
 
 dcPVCSubStatus OBJECT-TYPE
        SYNTAX INTEGER {
                unknown(1),
                notAvailable(2),
                mppt(3),
                voltageMode(4),
                outputCurrentLimit(5),
                outputPowerLimit(6),
                inputCurrentLimit(7),
                inputPowerLimit(8),
                inputVoltageOutsideRange(9),
                sunset(10),
                breakerOpen(11),
                startUpDelay(12),
                otp(13),
                ovp(14),
                fanFailure(15) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Specifies sub-status of PVCs."
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.5 -- 
 ::= { dcPVCEntry 5 }
 
 dcPVCConfiguration OBJECT-TYPE
        SYNTAX INTEGER {
                unknown(1),
                ok(2),
                default(3),
                outsideLimts(4),
                invalid(5) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Specifies configuration of PVCs."
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.6 -- 
 ::= { dcPVCEntry 6 }
 
 dcPVCIout OBJECT-TYPE
        SYNTAX Integer32
        UNITS "100 mA"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The measured PVC output current. The max. value 2147483647 
                is used to indicate an invalid value."
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.7 -- 
 ::= { dcPVCEntry 7 }
 
 dcPVCUout OBJECT-TYPE
        SYNTAX Integer32
        UNITS "10 mV"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The measured PVC output voltage. The max. value 2147483647 
                is used to indicate an invalid value."
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.8 -- 
 ::= { dcPVCEntry 8 }
 
  dcPVCIin OBJECT-TYPE
        SYNTAX Integer32
        UNITS "100 mA"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The measured PVC input current. The max. value 2147483647 
                is used to indicate an invalid value."
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.9 -- 
 ::= { dcPVCEntry 9 }
 
 dcPVCUin OBJECT-TYPE
        SYNTAX Integer32
        UNITS "100 mV"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The measured PVC input voltage. The max. value 2147483647 
                is used to indicate an invalid value."
   -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.4.1.10 -- 
 ::= { dcPVCEntry 10 }
    
-- ====================================================================
-- PVC Group table
-- ====================================================================
dcPVCGroupTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcPVCGroupEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table that shows all available PVC groups."
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5 -- 
 ::= { dcPVC 5 }

dcPVCGroupEntry OBJECT-TYPE
        SYNTAX DcPVCGroupEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular PVC group entry."
        INDEX { dcPVCGroupIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1 --  
 ::= { dcPVCGroupTable 1 }

DcPVCGroupEntry ::= SEQUENCE {
        dcPVCGroupIndex Integer32, 
        dcPVCGroupPVCType INTEGER,
        dcPVCGroupVoltage Integer32,
        dcPVCGroupVPGM Integer32,
        dcPVCGroupInputLowOff Integer32,
        dcPVCGroupInputLowOn Integer32,
        dcPVCGroupStartUpDelay Gauge32,
        dcPVCGroupOvpLimit Integer32,
        dcPVCGroupAlarmDelay Gauge32}

dcPVCGroupIndex OBJECT-TYPE
        SYNTAX Integer32 (1..1)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.1 --  
 ::= { dcPVCGroupEntry 1 }
                               
dcPVCGroupPVCType OBJECT-TYPE
        SYNTAX INTEGER {
                unknown48V(1), 
                pvc2200B48(2)}
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "PVC type defined for this group." 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.2 -- 
 ::= { dcPVCGroupEntry 2 }

dcPVCGroupVoltage OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "This default voltage is used by PVCs when there 
                is no connection to ORION."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.3 -- 
 ::= { dcPVCGroupEntry 3 }
 
 dcPVCGroupVPGM OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "This is offset voltage used by PVCs." 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.4 -- 
 ::= { dcPVCGroupEntry 4 }

dcPVCGroupInputLowOff OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "100 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Threshold for low input voltage."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.5 --  
 ::= { dcPVCGroupEntry 5 }
    
dcPVCGroupInputLowOn OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "100 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Threshold for low input voltage."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.6 --    
 ::= { dcPVCGroupEntry 6 }

dcPVCGroupStartUpDelay OBJECT-TYPE
        SYNTAX Gauge32 
        UNITS "seconds"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "This parameter is power up time of PVC that can be defined."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.7 --    
 ::= { dcPVCGroupEntry 7 }

dcPVCGroupOvpLimit OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "10 mV"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "This voltage defines the maximum allowed DC-voltage."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.8 -- 
 ::= { dcPVCGroupEntry 8}

dcPVCGroupAlarmDelay OBJECT-TYPE
        SYNTAX Gauge32 
        UNITS "seconds"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "This parameter can be used for suppressing alarms during night time."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1.9 --    
 ::= { dcPVCGroupEntry 9 }

                                    
-- ====================================================================
-- Inventory table
-- ====================================================================
dcInventoryTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcInventoryEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Controller's inventory table that shows all inventory information. "
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1 --  
 ::= { dcInventory 1 }

dcInventoryEntry OBJECT-TYPE
        SYNTAX DcInventoryEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular inventory entry."
        INDEX { dcInventoryIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1 --  
 ::= { dcInventoryTable 1 }

DcInventoryEntry ::= SEQUENCE {

        dcInventoryIndex        Integer32,
        dcInventoryType         DisplayString,
        dcInventoryName         DisplayString,
        dcInventorySwVersion    DisplayString,
        dcInventoryBuildVersion DisplayString,
        dcInventoryPartNb       DisplayString,
        dcInventorySerialNb     DisplayString,
        dcInventoryTopLevel     DisplayString}
        

dcInventoryIndex OBJECT-TYPE
        SYNTAX Integer32 (1..10000)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.1 --  
 ::= { dcInventoryEntry 1 }

dcInventoryType OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..32))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Module type"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.2 --  
 ::= { dcInventoryEntry 2 }

dcInventoryName OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..32))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Module name"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.3 --  
 ::= { dcInventoryEntry 3 }

dcInventorySwVersion OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..32))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Module software vision"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.4 --  
 ::= { dcInventoryEntry 4 }
 
dcInventoryBuildVersion OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..32))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Module software build vision"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.5 --  
 ::= { dcInventoryEntry 5 }
 
dcInventoryPartNb OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..32))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Module part number"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.6 --  
 ::= { dcInventoryEntry 6 }
 
dcInventorySerialNb OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..32))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Module serial number"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.7 --  
 ::= { dcInventoryEntry 7 }
 
dcInventoryTopLevel OBJECT-TYPE
        SYNTAX DisplayString (SIZE (1..32))
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Module top level"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.12.1.1.8 --  
 ::= { dcInventoryEntry 8 }

-- ====================================================================
-- Aircon table
-- ====================================================================
dcAirconTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcAirconEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Aircon table that shows all Aircon and cooling plan information. "
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1 --  
 ::= { dcAircon 1 }

dcAirconEntry OBJECT-TYPE
        SYNTAX DcAirconEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular Aircon entry."
        INDEX { dcAirconIndex, dcCoolingPlanIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1 --  
 ::= { dcAirconTable 1 }

DcAirconEntry ::= SEQUENCE {

        dcAirconIndex                Integer32,
        dcCoolingPlanIndex           Integer32,
		dcAirconName                 DisplayString,
		dcAirconMainStatus           INTEGER,
		dcAirconSubStatus            INTEGER,
		dcAirconConfiguration        INTEGER,
		dcAirconPlanName             DisplayString,
		dcAirconRoomTemp             Integer32,
        dcCoolingPlanActivationInput DisplayString,
        dcCoolingPlanPriority        INTEGER,
        dcCoolingPlanStatus          INTEGER,
		dcCoolingPlanTargetTemp      Integer32,
		dcCoolingPlanOperatingMode   INTEGER,
		dcCoolingPlanStandbyFanSpeed INTEGER,
		dcCoolingPlanHeaterStartTemp Integer32,
		dcCoolingPlanHeaterHyst      Integer32,
        dcCoolingPlanHeaterControl   INTEGER}
        

dcAirconIndex OBJECT-TYPE
        SYNTAX Integer32 (1..10000)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.1 --  
 ::= { dcAirconEntry 1 }

dcCoolingPlanIndex OBJECT-TYPE
        SYNTAX Integer32 (1..10000)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Cooling plan index"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.2 --  
 ::= { dcAirconEntry 2 }

dcAirconName OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Aircon module name"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.3 --  
 ::= { dcAirconEntry 3 }
 
dcAirconMainStatus OBJECT-TYPE
        SYNTAX INTEGER {
                unknown(1),
                on(2),
                remoteOff(3),
                standby(4),
                warning(5),
                temporaryInternalOff(6) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Aircon module main status"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.4 --  
 ::= { dcAirconEntry 4 }

dcAirconSubStatus OBJECT-TYPE
        SYNTAX INTEGER {
                na(1),
                unknown(2),
                cooling(3),
                silentCooling(4),
                selfTest(5),
                heating(6),
                targetTemperatureReached(7),
                localOff(8),
                forceVentilation(9),
                systemProtection(10),
                temperatureAbnormal(11),
                temperatureSensorFault(12),
                fanFault(13),
                controlDeviceFault(14),
				heatExchangeSystemFault(14),
                environmentalAbnormalAlarm(15) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Aircon module sub status"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.5 --  
 ::= { dcAirconEntry 5 }
 
dcAirconConfiguration OBJECT-TYPE
        SYNTAX INTEGER {
                ok(1),
                default(2),
                outsideLimit(3),
                invalid(4) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Module configuration status"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.6 --  
 ::= { dcAirconEntry 6 }
 
dcAirconPlanName OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The name of cooling plan"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.7 --  
 ::= { dcAirconEntry 7 }
 
dcAirconRoomTemp OBJECT-TYPE
        SYNTAX Integer32
		UNITS "0.1 degree"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Room temperature"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.8 --  
 ::= { dcAirconEntry 8 }
 
dcCoolingPlanActivationInput OBJECT-TYPE
        SYNTAX DisplayString
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The input event for activate cooling plan"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.9 --  
 ::= { dcAirconEntry 9 }
 
dcCoolingPlanPriority OBJECT-TYPE
        SYNTAX INTEGER {
                priority1(1),
                priority2(2),
                priority3(3),
                priority4(4),
				priority5(5),
                lowest(6) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Cooling plan priority"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.10 --  
 ::= { dcAirconEntry 10 }
 
dcCoolingPlanStatus OBJECT-TYPE
        SYNTAX INTEGER {
                inactive(1),
				active(2),
                suppressed(3) }
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Cooling plan status"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.11 --  
 ::= { dcAirconEntry 11 }
 
dcCoolingPlanTargetTemp OBJECT-TYPE
        SYNTAX Integer32 (250..1040)
		UNITS "0.1 degree"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Cooling plan target temperature. The range is 25°C ... 40°C(77°F ... 104°F)."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.12 --  
 ::= { dcAirconEntry 12 }
 
dcCoolingPlanOperatingMode OBJECT-TYPE
        SYNTAX INTEGER {
                normal(1),
				silent(2),
                off(3) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Cooling plan operating mode"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.13 --  
 ::= { dcAirconEntry 13 }
 
dcCoolingPlanStandbyFanSpeed OBJECT-TYPE
        SYNTAX INTEGER {
				low(2),
                high(3) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Cooling plan standby fan speed"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.14 --  
 ::= { dcAirconEntry 14 }
 
dcCoolingPlanHeaterStartTemp OBJECT-TYPE
        SYNTAX Integer32 (-100..590)
		UNITS "0.1 degree"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Cooling plan heater start temperature. The range is -10°C ... 15°C(14°F ... 59°F)."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.15 --  
 ::= { dcAirconEntry 15 }
 
dcCoolingPlanHeaterHyst OBJECT-TYPE
        SYNTAX Integer32 (10..180)
		UNITS "0.1 degree"
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Cooling plan heater start temperature hysteresis. The range is 1°C ... 10°C(1.8°F ... 18°F)."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.16 --  
 ::= { dcAirconEntry 16 }
 
dcCoolingPlanHeaterControl OBJECT-TYPE
        SYNTAX INTEGER {
                auto(1),
                manual(2) }
        MAX-ACCESS read-write
        STATUS current
        DESCRIPTION
                "Cooling plan heater control mode"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.14.1.1.17 --  
 ::= { dcAirconEntry 17 }
 
-- ====================================================================
-- Inverter Group table
-- ====================================================================
dcInverterGroupTable OBJECT-TYPE
        SYNTAX SEQUENCE OF DcInverterGroupEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table that shows all available Inverter groups."
-- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1 -- 
 ::= { dcInverter 1 }

dcInverterGroupEntry OBJECT-TYPE
        SYNTAX DcInverterGroupEntry
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "A particular Inverter group entry."
        INDEX { dcInverterGroupIndex }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.11.5.1 --  
 ::= { dcInverterGroupTable 1 }

DcInverterGroupEntry ::= SEQUENCE {
        dcInverterGroupIndex Integer32, 
        dcInverterGroupState INTEGER,
		dcInverterGroupLoadPosition INTEGER,
        dcInverterGroupNbrOfConfigInverters Gauge32,
		dcInverterGroupNbrOfPresentInverters Gauge32,        
		dcInverterGroupPhase Gauge32,
		dcInverterGroupDcVoltage Integer32,
		dcInverterGroupInputDcPower Integer32,
		dcInverterGroupInputVoltage1 Integer32,
		dcInverterGroupInputVoltage2 Integer32,
		dcInverterGroupInputVoltage3 Integer32,
		dcInverterGroupInputApparentPower1 Integer32,
		dcInverterGroupInputApparentPower2 Integer32,
		dcInverterGroupInputApparentPower3 Integer32,
		dcInverterGroupInputFrequency Gauge32,
		dcInverterGroupOutputVoltage1 Integer32,
		dcInverterGroupOutputVoltage2 Integer32,
		dcInverterGroupOutputVoltage3 Integer32,
		dcInverterGroupOutputApparentPower1 Integer32,
		dcInverterGroupOutputApparentPower2 Integer32,
		dcInverterGroupOutputApparentPower3 Integer32,
		dcInverterGroupOutputFrequency Gauge32}

dcInverterGroupIndex OBJECT-TYPE
        SYNTAX Integer32 (1..1)
        MAX-ACCESS not-accessible
        STATUS current
        DESCRIPTION
                "Table index."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.1 --  
 ::= { dcInverterGroupEntry 1 }
                               
dcInverterGroupState OBJECT-TYPE
        SYNTAX INTEGER {
                invalid(1),
                noAlarm(2),
                nonUrgentAlarm(3),
                urgentAlarm(4)}
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "This is the alarm state of the inverter system." 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.2 -- 
 ::= { dcInverterGroupEntry 2 }
 
dcInverterGroupLoadPosition OBJECT-TYPE
        SYNTAX INTEGER {
                invalid(1),
                ac(2),
				dc(3),
				mixed(4),
				unknown(5)}
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Shows where is the load positioned in the system." 
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.3 -- 
 ::= { dcInverterGroupEntry 3 }
                                
dcInverterGroupNbrOfConfigInverters OBJECT-TYPE
        SYNTAX Gauge32 
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "The system is configure to operate this number of inverters at maximum."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.4 --    
 ::= { dcInverterGroupEntry 4 }
                                
dcInverterGroupNbrOfPresentInverters OBJECT-TYPE
        SYNTAX Gauge32 
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Number of inverters actually present in the system."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.5 --    
 ::= { dcInverterGroupEntry 5 }            
                
dcInverterGroupPhase OBJECT-TYPE
        SYNTAX Gauge32 
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "This is the alarm state of the inverter system."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.6 --    
 ::= { dcInverterGroupEntry 6 }
 
dcInverterGroupDcVoltage OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "10 mV"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Input DC voltage"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.7 -- 
 ::= { dcInverterGroupEntry 7 }
 
dcInverterGroupInputDcPower OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "1 W"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Input DC Power"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.8 -- 
 ::= { dcInverterGroupEntry 8 }
 
dcInverterGroupInputVoltage1 OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "100 mV"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Input voltage line 1"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.9 -- 
 ::= { dcInverterGroupEntry 9 }
 
dcInverterGroupInputVoltage2 OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "100 mV"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Input voltage line 2 - in three phase system only"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.10 -- 
 ::= { dcInverterGroupEntry 10 }
 
dcInverterGroupInputVoltage3 OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "100 mV"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Input voltage line 3 - in three phase system only"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.11 -- 
 ::= { dcInverterGroupEntry 11 }
 
dcInverterGroupInputApparentPower1 OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "1 VA"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Input power line 1"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.12 -- 
 ::= { dcInverterGroupEntry 12 }
 
dcInverterGroupInputApparentPower2 OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "1 VA"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Input power line 2 - in three phase system only"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.13 -- 
 ::= { dcInverterGroupEntry 13 }
 
dcInverterGroupInputApparentPower3 OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "1 VA"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Input power line 3 - in three phase system only"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.14 -- 
 ::= { dcInverterGroupEntry 14 }
  
dcInverterGroupInputFrequency OBJECT-TYPE
        SYNTAX Gauge32 
        UNITS "10 mHz"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Input frequency"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.15 --    
 ::= { dcInverterGroupEntry 15 }
 
dcInverterGroupOutputVoltage1 OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "100 mV"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Output voltage line 1"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.16 -- 
 ::= { dcInverterGroupEntry 16 }
 
dcInverterGroupOutputVoltage2 OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "100 mV"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Output voltage line 2 - in three phase system only"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.17 -- 
 ::= { dcInverterGroupEntry 17 }
 
dcInverterGroupOutputVoltage3 OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "100 mV"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Output voltage line 3 - in three phase system only"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.18 -- 
 ::= { dcInverterGroupEntry 18 }
 
dcInverterGroupOutputApparentPower1 OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "1 VA"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Output apparent power line 1"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.19 -- 
 ::= { dcInverterGroupEntry 19 }
 
dcInverterGroupOutputApparentPower2 OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "1 VA"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Output apparent power line 2 - in three phase system only"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.20 -- 
 ::= { dcInverterGroupEntry 20 }
 
dcInverterGroupOutputApparentPower3 OBJECT-TYPE
        SYNTAX Integer32 
        UNITS "1 VA"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Output apparent power line 3 - in three phase system only"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.21 -- 
 ::= { dcInverterGroupEntry 21 }
 
dcInverterGroupOutputFrequency OBJECT-TYPE
        SYNTAX Gauge32 
        UNITS "10 mHz"
        MAX-ACCESS read-only
        STATUS current
        DESCRIPTION
                "Output frequency"
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.2.15.1.1.22 --    
 ::= { dcInverterGroupEntry 22 }
 
-- ====================================================================
-- Notifications
-- ====================================================================
systemNonUrgentAlarm NOTIFICATION-TYPE
        OBJECTS {
                dcSiteName,
                dcSystemName,
                dcSystemDateTime,
                dcNumberNonUrgentAlarms,
                dcNonUrgentAlarmIdentifier,
                dcNonUrgentAlarmValue,
                dcNonUrgentAlarmName }
        STATUS current
        DESCRIPTION
                "The controller reports that one or more elements have changed
                into none urgent alarm state."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.1 --  
 ::= { controllerEventsV2 1 }

systemUrgentAlarm NOTIFICATION-TYPE
        OBJECTS {                        
                dcSiteName,
                dcSystemName,
                dcSystemDateTime,
                dcNumberUrgentAlarms,
                dcUrgentAlarmIdentifier,
                dcUrgentAlarmValue,
                dcUrgentAlarmName }
        STATUS current
        DESCRIPTION
                "The controller reports that one or more elements have changed
                into urgent alarm state."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.2 --  
 ::= { controllerEventsV2 2 }

systemCriticalAlarm NOTIFICATION-TYPE
        OBJECTS {
                dcSiteName,
                dcSystemName,
                dcSystemDateTime,
                dcNumberCriticalAlarms,
                dcCriticalAlarmIdentifier,
                dcCriticalAlarmValue,
                dcCriticalAlarmName }
        STATUS current
        DESCRIPTION
                "The controller reports that one or more elements have changed
                into critical alarm state."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.3 --  
 ::= { controllerEventsV2 3 }
 
systemAllAlarm NOTIFICATION-TYPE
        OBJECTS {
                dcSiteName,
                dcSystemName,
                dcSystemDateTime,
                dcNumberAllAlarms,
                dcAllAlarmIdentifier,
                dcAllAlarmValue,
                dcAllAlarmName }
        STATUS current
        DESCRIPTION
                "The controller reports that one Alarm Event state has changed."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.3.1.0.4 --  
 ::= { controllerEventsV2 4 }
                                         
-- ====================================================================
-- Conformance area, containing groups and compliance specifications
-- ====================================================================
systemInfoGroup OBJECT-GROUP
        OBJECTS {
                dcSiteName,
                dcSystemName,
                dcSystemDateTime,
                dcSoftwareVersion,
                dcCreateInventoryReport }
        STATUS current
        DESCRIPTION
                "The collection of system info scalar objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.1 --  
 ::= { controllerGroups 1 }

systemAlarmGroup OBJECT-GROUP
        OBJECTS {
                dcNumberUrgentAlarms,
                dcNumberNonUrgentAlarms,
                dcMainsFailureAlarm,
                dcUrgentAlarmIdentifier,
                dcUrgentAlarmValue,
                dcNonUrgentAlarmIdentifier,
                dcNonUrgentAlarmValue,
                dcUrgentAlarmName,
                dcNonUrgentAlarmName,
                dcNumberCriticalAlarms,
                dcCriticalAlarmIdentifier,
                dcCriticalAlarmValue,
                dcCriticalAlarmName,
				dcNumberAllAlarms,
				dcAllAlarmIdentifier,
                dcAllAlarmValue,
                dcAllAlarmName }
        STATUS current
        DESCRIPTION
                "The collection of system alarm scalar objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.2 --  
 ::= { controllerGroups 2 }

systemMonitorGroup OBJECT-GROUP
        OBJECTS {
                dcSystemVoltage,
                dcLoadCurrent,
                dcBatteryCurrent,
                dcBatteryTemperature,
                dcChargeState,
                dcCurrentLimit,
                dcRectifierCurrent,
                dcSystemPower }
        STATUS current
        DESCRIPTION
                "The collection of system monitor scalar objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.3 --  
 ::= { controllerGroups 3 }

rectifierGroup OBJECT-GROUP
        OBJECTS {
                dcNumberRectifiers,
                dcNumberRectifiersFailure,
                dcNumberRectifiersOkay,
                dcEfficiencyCyclingEnabled,
                dcLimitSwitchingTimes,
                dcForceCyclingType,
                dcMinimumPowerReserve,
                dcMinimumRectifierPower }
        STATUS current
        DESCRIPTION
                "The collection of rectifier scalar objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.4 --  
 ::= { controllerGroups 4 }

eventHistoryTableGroup OBJECT-GROUP
        OBJECTS {
                dcEventHistoryTimestamp,
                dcEventHistoryMessage }
        STATUS current
        DESCRIPTION
                "The collection of event history table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.5 --  
 ::= { controllerGroups 5 }

alarmTableGroup OBJECT-GROUP
        OBJECTS {
                dcAlarmEventCategory,
                dcAlarmEventName,
                dcAlarmEventIdentifier,
                dcAlarmEventValue }
        STATUS current
        DESCRIPTION
                "The collection of alarm table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.6 --  
 ::= { controllerGroups 6 }

rectifierTableGroup OBJECT-GROUP
        OBJECTS {
                dcRectifierIdentifier,
                dcRectifierSlotState,
                dcRectifierMainStatus,
                dcRectifierConfiguration,
                dcRectifierIout,
                dcRectifierPout }
        STATUS current
        DESCRIPTION
                "The collection of rectifier table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.7 --  
 ::= { controllerGroups 7 }

notificationsGroup NOTIFICATION-GROUP
        NOTIFICATIONS {
                systemNonUrgentAlarm,
                systemUrgentAlarm,
                systemCriticalAlarm,
				systemAllAlarm }
        STATUS current
        DESCRIPTION
                "The group of all controller notifications."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.8 --  
 ::= { controllerGroups 8 }   
 
genericAlarmTableGroup OBJECT-GROUP
        OBJECTS {
                dcGenericAlarmEventIdentifier,
                dcGenericAlarmEventName,
                dcGenericAlarmEventValue }
        STATUS current
        DESCRIPTION
                "Assignment of events to alarm table entries."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.9 --  
 ::= { controllerGroups 9 }        
 
batteryGroup OBJECT-GROUP
        OBJECTS {
            dcUsys20,
            dcTempCompType,
            dcSlope,
            dcStartTemp,
            dcStopTemp,
            dcMaxVoltage,
            dcLowStopVoltage,
            dcLowStartTemp,
            dcLowTempSlope,
            dcHighStartTemp,
            dcHighTempSlope,
            dcHighStopVoltage,
            dcRunawayTemp,
            dcRunawayVoltage,
            dcBatteryTestUsupport,
            dcBatteryTestDuration,
            dcBatteryTestInterval,
            dcBatteryTestDischargeCurrent,
            dcBatteryTestMinDuration,
            dcBatteryTestVoltageWithinUfloat,
            dcBatteryTestVoltageWithinUfloatPeriod,
            dcBatteryTestTempFrom,
            dcBatteryTestTempTo,
            dcBatteryTestIntervalEnabled,
            dcBatteryTestStartTimeFrom,
            dcBatteryTestStartTimeTo,
            dcBatteryTestDateTime,
            dcBatteryTestResult,
            dcBatteryTestEndVoltage,
            dcBatteryTestControl,
            dcBatteryTestStatus,
            dcBatteryTestFailureEvent,
            dcBatteryTestType,
            dcTotalBatteryCapacity, 
            dcBatteryLifePredictionStatus,
            dcBatteryChargingCurrentLimitEnable,
            dcBatteryTotalChargingCurrentLimitEnable,
            dcBatteryTotalMaxIBatt,
            dcLossOfBackupTimeEnabled,
            dcLossOfBackupTimeStatus,
            dcExpectedBackupTime,
            dcEqualizeControl,
            dcEqualizeStatus,
            dcEqualizeEnabled,
            dcEqualizeVoltage,
            dcEqualizeDuration,
            dcEqualizeUseBattRoomFanEnabled,
            dcEqualizeLeadTime,
            dcEqualizeTimeLag,
            dcEqualizeInterval,
            dcEqualizeStartTimeIntervalFrom,
            dcEqualizeStartTimeIntervalTo,
            dcEqualizeInhibitAfterBoost,
            dcBoostChargeControl,
            dcBoostChargeStatus,
            dcBoostChargeType,
            dcBoostChargeVoltage,
            dcBoostChargeMaxDuration,
            dcBoostChargeUseBattRoomFanEnabled,
            dcBoostChargeTimeLag,
            dcBoostChargeIstart,
            dcBoostChargeIstop,
            dcBoostChargeInhibitTime,
			dcBoostChargeSoCBelow,
            dcUaMax,
            dcUaMin,
            dcUsMax,
            dcUsMin,
            dcBoD,
            dcHysteresis,
            dcSuppressUaLowEnabled,
            dcSuppressUsLowEnabled,
            dcEnableUsTempComp,
            dcEvtCtrlChargeStatus,
            dcEvtCtrlChargeType,
            dcEvtCtrlChargeVoltage,
            dcEvtCtrlChargeTempCompEnabled,
            dcEvtCtrlChargeMaxIBatt,
            dcHighTemp,
            dcHighTempHyst,
            dcBatteryTypeSelect }
        STATUS current
        DESCRIPTION
                "The collection of battery scalar objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.10 --  
 ::= { controllerGroups 10 }
                                      
controlEventTableGroup
  OBJECT-GROUP
        OBJECTS {
                dcControlEventName,
                dcControlEventIdentifier,
                dcControlEventValue }
        STATUS current
        DESCRIPTION
                "Assignment of control events to table entries."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.11 --  
 ::= { controllerGroups 11 }
                                   
trapDestinationTableGroup  
  OBJECT-GROUP
        OBJECTS {
                dcTrapDestinationIp,
                dcTrapDestinationPort,
                dcTrapDestinationUser }
        STATUS current
        DESCRIPTION
                "Trap destionation table."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.12 --  
 ::= { controllerGroups 12 }
       
miscGroup OBJECT-GROUP
        OBJECTS {
                dcFileProcessingStatus,
                dcResendActiveAlarmTraps,
                dcRebootController }
        STATUS current
        DESCRIPTION
                "The collection of miscellaneous objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.13 --  
 ::= { controllerGroups 13 }
     
rectifierGroupTableGroup OBJECT-GROUP
        OBJECTS {
                dcRectifierGroupName,
                dcRectifierGroupRectifierType,
                dcRectifierGroupDefaultVoltage,
                dcRectifierGroupDefaultCurrentLimit,
                dcRectifierGroupDefaultPowerLimit,
                dcRectifierGroupInputLowOff,
                dcRectifierGroupInputLowOn,
                dcRectifierGroupStartupVoltage,
                dcRectifierGroupStartupCurrentLimit,
                dcRectifierGroupStartupPowerLimit,
                dcRectifierGroupStartupLimitTime,
                dcRectifierGroupPowerupDelay,
                dcRectifierGroupPowerupTime,
                dcRectifierGroupUmaxOff }
        STATUS current
        DESCRIPTION
                "The collection of rectifier group table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.14 --  
 ::= { controllerGroups 14 }

batteryStringTableGroup OBJECT-GROUP
        OBJECTS {
                dcBatteryStringName,
                dcBatteryStringMaxIBatt,
                dcBatteryStringCapacity }
        STATUS current
        DESCRIPTION
                "The collection of battery string table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.15 --  
 ::= { controllerGroups 15 }

defaultLogEventTableGroup OBJECT-GROUP
        OBJECTS {
                dcDefaultLogEventName,
                dcDefaultLogEventLogged }
        STATUS current
        DESCRIPTION
                "The collection of default log event table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.16 --  
 ::= { controllerGroups 16 }

eventProcessingEventTableGroup OBJECT-GROUP
        OBJECTS {
                dcEventProcessingEventName,
                dcEventProcessingEventAssigned,
                dcEventProcessingEventType,
                dcEventProcessingEventSelected }
        STATUS current
        DESCRIPTION
                "The collection of event processing event table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.17 --  
 ::= { controllerGroups 17 }

lvdTableGroup OBJECT-GROUP
        OBJECTS {
                dcLvdName,
                dcLvdDisconnectDelay, 
				dcLvdType, 
				dcLvdVoltageThreshold,	
				dcLvdVoltageHysteresis,	
				dcLvdControlEvent,
				dcLvdMonitoringEvent }
        STATUS current
        DESCRIPTION
                "The collection of LVD table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.18 --  
 ::= { controllerGroups 18 }     
 
powerLimitationTableGroup OBJECT-GROUP
        OBJECTS {
                dcPowerLimitationEventName,
                dcPowerLimitationStatus,
                dcPowerLimitationType,
                dcMaxTotalRectifierPower,
                dcPowerLimitationNoBatteryDischarge }
        STATUS current
        DESCRIPTION
                "The collection of power limitation table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.19 --  
 ::= { controllerGroups 19 }   

measurementTableGroup OBJECT-GROUP
        OBJECTS {
                dcMeasurementName,
                dcMeasurementValue,
                dcMeasurementScaleFactor,
                dcMeasurementUnit }      
        STATUS current
        DESCRIPTION
                "The collection of measurement table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.20 --  
 ::= { controllerGroups 20 }   

meterPanelEventTableGroup OBJECT-GROUP
        OBJECTS {
                dcMeterPanelEventName,
                dcMeterPanelEventValue,
                dcMeterPanelEventHourMeterValue }      
        STATUS current
        DESCRIPTION
                "The collection of meter panel event table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.21 --  
 ::= { controllerGroups 21 }    
 
meterPanelmeasurementTableGroup OBJECT-GROUP
        OBJECTS {
                dcMeterPanelMeasurementName,
                dcMeterPanelMeasurementValue,
                dcMeterPanelMeasurementUnit }      
        STATUS current
        DESCRIPTION
                "The collection of meter panel measurement table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.22 --  
 ::= { controllerGroups 22 }    
                             
batteryLithiumTableGroup OBJECT-GROUP
        OBJECTS {       
                dcBatteryLithiumName,
                dcBatteryLithiumMainState,
                dcBatteryLithiumSubState,                
                dcBatteryLithiumCurrent,
                dcBatteryLithiumStateOfCharge,
                dcBatteryLithiumInstallationDate,
                dcBatteryLithiumSoH }
        STATUS current
        DESCRIPTION
                "The collection of Lithium battery table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.23 --  
 ::= { controllerGroups 23 }
 
batteryLifePredictionTableGroup OBJECT-GROUP
        OBJECTS {   
                dcBatteryLifePredictionName,
                dcBatteryLifePredictionRemainingDays,
                dcBatteryLifePredictionInstallationDate,
                dcBatteryLifePredictionSoH }
        STATUS current
        DESCRIPTION
                "The collection of battery life prediction table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.24 --  
 ::= { controllerGroups 24 }
          
pvcGroup OBJECT-GROUP
        OBJECTS {
                dcNumberPVCs,
                dcNumberPVCsFailure,
                dcNumberPVCsOkay  }
        STATUS current
        DESCRIPTION
                "The collection of PVC scalar objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.25 --  
 ::= { controllerGroups 25 }
 
pvcTableGroup OBJECT-GROUP
        OBJECTS {
                dcPVCIdentifier, 
                dcPVCSlotState, 
                dcPVCMainStatus,
                dcPVCSubStatus,
                dcPVCConfiguration,
                dcPVCIout,
                dcPVCUout,
                dcPVCIin,
                dcPVCUin}
        STATUS current
        DESCRIPTION
                "The collection of PVC table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.26 --  
 ::= { controllerGroups 26 }
          
pvcGroupTableGroup OBJECT-GROUP
        OBJECTS {
                dcPVCGroupPVCType,
                dcPVCGroupVoltage,
                dcPVCGroupVPGM,
                dcPVCGroupInputLowOff,
                dcPVCGroupInputLowOn,
                dcPVCGroupStartUpDelay,
                dcPVCGroupOvpLimit,
                dcPVCGroupAlarmDelay}
        STATUS current
        DESCRIPTION
                "The collection of PVC Group table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.27 --  
 ::= { controllerGroups 27 }          
 
inventoryTableGroup OBJECT-GROUP
        OBJECTS {
                dcInventoryType,
                dcInventoryName,
                dcInventorySwVersion,
                dcInventoryBuildVersion,
                dcInventoryPartNb,
                dcInventorySerialNb,
                dcInventoryTopLevel }
        STATUS current
        DESCRIPTION
                "The collection of inventory table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.28 --  
 ::= { controllerGroups 28 }
 
eventDefinitionTableGroup OBJECT-GROUP
        OBJECTS {
                dcEventName,
				dcThreshold,
				dcThresholdHysteresis,
                dcUnit }
        STATUS current
        DESCRIPTION
                "The collection of event definition table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.29 --  
 ::= { controllerGroups 29 }
 
filterTableGroup OBJECT-GROUP
        OBJECTS {
                dcFilterName,
				dcTrueForMin,
                dcFalseForMin }
        STATUS current
        DESCRIPTION
                "The collection of Filter table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.30 --  
 ::= { controllerGroups 30 } 
 
timerTableGroup OBJECT-GROUP
        OBJECTS {
                dcTimerName,
				dcStartTime,
				dcStartDaySu,
				dcStartDayMo,
				dcStartDayTu,
				dcStartDayWe,
				dcStartDayTh,
				dcStartDayFr,
				dcStartDaySa,
				dcEndTime,
				dcEndDaySu,
				dcEndDayMo,
				dcEndDayTu,
				dcEndDayWe,
				dcEndDayTh,
				dcEndDayFr,			
                dcEndDaySa }
        STATUS current
        DESCRIPTION
                "The collection of timer table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.31 --  
 ::= { controllerGroups 31 } 

ipGroup OBJECT-GROUP
        OBJECTS {
                dcIPv4Address,
                dcIPv4SubnetMask,
                dcIPv4Gateway,
                dcIPv4DNS,
                dcIPv6LinkLocalAddress,
                dcIPv6Address,
                dcIPv6Gateway,
				dcIPv6DNSAuto,
                dcIPv6DNSManual }
        STATUS current
        DESCRIPTION
                "The collection of ip objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.32 --  
 ::= { controllerGroups 32 }
 
newTrapDestinationTableGroup  
        OBJECT-GROUP
        OBJECTS {
                dcTrapDestinationv2,
                dcTrapDestinationv2Port,
                dcTrapDestinationv2User }
        STATUS current
        DESCRIPTION
                "New Trap destionation table."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.33 --  
 ::= { controllerGroups 33 }

airconTableGroup  
        OBJECT-GROUP
        OBJECTS {
                dcAirconName,
                dcAirconMainStatus,
				dcAirconSubStatus,
				dcAirconConfiguration,
				dcAirconPlanName,
				dcAirconRoomTemp ,
				dcCoolingPlanActivationInput,
				dcCoolingPlanPriority,
				dcCoolingPlanStatus,
				dcCoolingPlanTargetTemp,
				dcCoolingPlanOperatingMode,
				dcCoolingPlanStandbyFanSpeed,
				dcCoolingPlanHeaterStartTemp,
				dcCoolingPlanHeaterHyst,
                dcCoolingPlanHeaterControl }
        STATUS current
        DESCRIPTION
                "Aircon table."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.34 --  
 ::= { controllerGroups 34 }

 inverterGroupTableGroup OBJECT-GROUP
        OBJECTS {
                                dcInverterGroupLoadPosition,
                                dcInverterGroupNbrOfConfigInverters,
                                dcInverterGroupNbrOfPresentInverters,
                                dcInverterGroupState,
                                dcInverterGroupPhase,
                                dcInverterGroupOutputVoltage1,
                                dcInverterGroupOutputVoltage2,
                                dcInverterGroupOutputVoltage3,
                                dcInverterGroupOutputApparentPower1,
                                dcInverterGroupOutputApparentPower2,
                                dcInverterGroupOutputApparentPower3,
                                dcInverterGroupOutputFrequency,
                                dcInverterGroupInputVoltage1,
                                dcInverterGroupInputVoltage2,
                                dcInverterGroupInputVoltage3,
                                dcInverterGroupInputApparentPower1,
                                dcInverterGroupInputApparentPower2,
                                dcInverterGroupInputApparentPower3,
                                dcInverterGroupInputFrequency,
                                dcInverterGroupDcVoltage,
                                dcInverterGroupInputDcPower}
        STATUS current
        DESCRIPTION
                "The collection of Inverter Group table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.35 --  
 ::= { controllerGroups 35 }

  eventCtrlChargeTableTableGroup OBJECT-GROUP
        OBJECTS {		dcEventControlledChargeTablePriority,
										dcEventControlledChargeTableName,
										dcEventControlledChargeTableActivationInput,
										dcEventControlledChargeTableStatus,
										dcEventControlledChargeTableType,
										dcEventControlledChargeTableVoltage,
										dcEventControlledChargeTableMaxIBatt,
										dcEventControlledChargeTableTempCompEnabled}
        STATUS current
        DESCRIPTION
                "The collection of Event Controlled Charge Table Group table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.36 --  
 ::= { controllerGroups 36 }

  batteryTestTableTableGroup OBJECT-GROUP
        OBJECTS {	dcBatteryTestTablePriority,
									dcBatteryTestTableName,
									dcBatteryTestTableType,
									dcBatteryTestTableStatus,
									dcBatteryTestTableUsupport,
									dcBatteryTestTableDuration,           
									dcBatteryTestTableInterval,
									dcBatteryTestTableDischargeCurrent,
									dcBatteryTestTableMinDuration,
									dcBatteryTestTableVoltageWithinUfloat,
									dcBatteryTestTableVoltageWithinUfloatPeriod,
									dcBatteryTestTableTempFrom,
									dcBatteryTestTableTempTo,
									dcBatteryTestTableIntervalEnabled,
									dcBatteryTestTableStartTimeFrom,
									dcBatteryTestTableStartTimeTo,
									dcBatteryTestTableControl,
									dcBatteryTestTableFailureEvent }
        STATUS current
        DESCRIPTION
                "The collection of Battery Test Table Group table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.37 --  
 ::= { controllerGroups 37 }

  batteryTestResultTableTableGroup OBJECT-GROUP
        OBJECTS {	dcBatteryTestResultTablePriority,
									dcBatteryTestResultTableName,
									dcBatteryTestResultTableDateTime,
									dcBatteryTestResultTableResult,
									dcBatteryTestResultTableEndVoltage }
        STATUS current
        DESCRIPTION
                "The collection of Battery Test Result Table Group table objects."
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.1.38 --  
 ::= { controllerGroups 38 }

controllerBasicCompl MODULE-COMPLIANCE
        STATUS current
        DESCRIPTION
                "The basic implementation requirements for the controller MIB."
        MODULE
        MANDATORY-GROUPS {
                systemInfoGroup,
                systemAlarmGroup,
                systemMonitorGroup,
                alarmTableGroup,
                notificationsGroup }
 -- 1.3.6.1.4.1.20246.2.3.1.1.1.1.2.1 --
 ::= { controllerCompl 1 }

END